CMS-660 SYSTEM
CIRCUIT MONITORING SYSTEM (CMS)
Sensor physical assignment time out, start procedure
This register [3001h] describes the time out after start of sensor physical assignment procedure during
control unit's start procedure. When control unit starts and doesn’t find any assigned sensors, the LED
“Status” blinks yellow and the user has the specified time to press the pushbutton of a sensor.
During the sensor physical assignment procedure, the delay time between Modbus request and
response can reach the time out value.
Default value 30 sec.
Sensor physical assignment time out, bus mode
This register [3002h] describes the time out after start of sensor physical assignment procedure.
When this procedure is started by command “add sensor” (see dedicated section), “remove sensor”
(see dedicated section) or “change sensor ID” (see dedicated section), the user has the specified time
to press the pushbutton of a sensor.
During the sensor physical assignment procedure, the delay time between Modbus request and
response can reach the time out value.
Default value 10 sec.
—
Modbus