CMS-660 SYSTEM
CIRCUIT MONITORING SYSTEM (CMS)
27
—
Modbus Mapping
Addr.
(hex)
Words
(16 bit)
Description
Resolution Unit
Format
Access
Ongoing measurement values:
These registers contain the actual measured data.
0000
1
TRMS value of Sensor 1
0.01
A
unsigned
R (03)
0001
1
TRMS value of Sensor 2
0.01
A
unsigned
R (03)
…
1
…
0.01
A
unsigned
R (03)
001E
1
TRMS value of Sensor 31
0.01
A
unsigned
R (03)
001F
1
TRMS value of Sensor 32
0.01
A
unsigned
R (03)
0100
1
AC value of Sensor 1
0.01
A
unsigned
R (03)
0101
1
AC value of Sensor 2
0.01
A
unsigned
R (03)
…
1
…
0.01
A
unsigned
R (03)
011E
1
AC value of Sensor 31
0.01
A
unsigned
R (03)
011F
1
AC value of Sensor 32
0.01
A
unsigned
R (03)
0200
1
DC value of Sensor 1
0.01
A
signed
R (03)
0201
1
DC value of Sensor 2
0.01
A
signed
R (03)
…
1
…
0.01
A
signed
R (03)
021E
1
DC value of Sensor 31
0.01
A
signed
R (03)
021F
1
DC value of Sensor 32
0.01
A
signed
R (03)
Minimum measured values:
These registers contain the minimum measured values since last system start or reset.
0400
1
TRMS min value of Sensor 1
0.01
A
unsigned
R (03)
0401
1
TRMS min value of Sensor 2
0.01
A
unsigned
R (03)
…
1
…
0.01
A
unsigned
R (03)
041E
1
TRMS min value of Sensor 31
0.01
A
unsigned
R (03)
041F
1
TRMS min value of Sensor 32
0.01
A
unsigned
R (03)
0500
1
AC min value of Sensor 1
0.01
A
unsigned
R (03)
0501
1
AC min value of Sensor 2
0.01
A
unsigned
R (03)
…
1
…
0.01
A
unsigned
R (03)
051E
1
AC min value of Sensor 31
0.01
A
unsigned
R (03)
051F
1
AC min value of Sensor 32
0.01
A
unsigned
R (03)
0600
1
DC min value of Sensor 1
0.01
A
signed
R (03)
0601
1
DC min value of Sensor 2
0.01
A
signed
R (03)
…
1
…
0.01
A
signed
R (03)
061E
1
DC min value of Sensor 31
0.01
A
signed
R (03)
061F
1
DC min value of Sensor 32
0.01
A
signed
R (03)