20
GAA610-M
ADVANCED EMISSION GAS MONITORING SYSTEM | OI/GAA610-M-EN REV. B
… 5 Preparation for Installation
Backpurging Unit
Design of the back-purging unit
The back-purging unit consists of a protective cabinet with shut-
off valve, 6 bar pressure reduction valve, solenoid valves for
back-purging, pressure regulator and 2 l compressed air receiver
(pressure buffer tank) for effective pressure pulses also with
lower airflow rate.
Distance to sampling probe
The distance between the back-purging unit and the sampling
probe should be as short as possible and must not exceed 2 m
(6.6 ft).
Protection from adverse ambient conditions
Protect the back-purging unit against:
• Water spray
• Contact with chemicals
• Strong sunlight and heat radiation
• Strong air currents
• Heavy dust load
• Corrosive atmospheres
• Vibration
Instrument air supply
Compressed air for back-purging
GAA610-M – Instrument air inlet conditions
Quality
Oil free, dry with dew point <
−
20 °C (
−
4 °F)
Pressure
Min. 400 kPa (60 psig)
Max. 600 kPa (90 psig)
Air consumption
< 0.2 Nm
3
/day
NOTICE
Damage to the sample conditioning components
If the compressed air is not dry and clean, this will result in
damage to the sample conditioning components (valves,
filters, sample gas cooler, sample gas feed unit) as well as to
the gas analyzer.
• Only use dry and clean compressed air.
Power supply
Power supply
Terminals
-X60
: L, N, PE or L1, L2, PE
Operating voltage
230 V AC, ±10 %
Frequency
50 / 60 Hz, ±3 Hz
External fuse
25 A
Power consumption
System cabinet
500 w
Air conditioner
1600 W
Sampling probe
300 W
Heated sample gas line
Approx. 90 W/m
Sample gas inlet conditions
DANGER
Explosion hazard
Explosion hazard when measuring ignitable gas / air or
gas / oxygen mixtures
• The gas analyzer may not be used for the measurement of
ignitable gas / air or gas / oxygen mixtures
GAA610-M – Sample gas inlet conditions
Temperature
Max. 500 °C (932 °F)
Pressure
850 to 1100 hPa (0.85 to 1.1 bar), (12.3 to 16 psi)
Содержание CEMcaptain GAA610-M
Страница 56: ...56 GAA610 M ADVANCED EMISSION GAS MONITORING SYSTEM OI GAA610 M EN REV B 11 Operation Menu structure...
Страница 97: ...GAA610 M ADVANCED EMISSION GAS MONITORING SYSTEM OI GAA610 M EN REV B 97 Location diagram...
Страница 98: ...98 GAA610 M ADVANCED EMISSION GAS MONITORING SYSTEM OI GAA610 M EN REV B 18Appendix Piping diagram...