background image

41-337.3L

6

4. CHARACTERISTICS

4.1.

CA-16 Bus Relay

This relay has variable percentage characteristics
which means that the operating coil current required
to close the relay contacts, expressed in percent of
the total restraint current, varies with the magnitude
of the restraint current.The relay sensitivity is high,
corresponding to a low percentage ratio, at light cur-
rents, and its sensitivity is low, corresponding to high
percentage unbalance, at high currents. The relay is
made sensitive at low currents in order to detect light
internal faults on the bus being protected. At the
same time, however, its reduced sensitivity at the
higher currents allows the various current transform-
ers involved to depart from their true ratio to a large
extent without causing false tripping of the relay for
external faults.

The variable percentage characteristics are particu-
larly advantageous when severe saturation of current

transformers is caused by the dc component of
asymmetrical short circuits. In the case of buses
located close to generating stations where the dc
components decay slowly, the breakdown in ratio of
the current transformers will be much greater than
would ever be expected from a consideration of the
usual ratio curves of the current transformers
involved.

The time of operation of the relays is shown in Figure
6.

4.2.

CA-26 Transformer Relay

The type CA-26 transformer differential relay
includes an indicating instantaneous trip unit (see
Figure 4), which operates on internal faults. The
instantaneous unit should have a setting equal to the
maximum rms symmetrical external fault current.
Such a setting will prevent operation of the instanta-
neous unit when a current transformer is severely
saturated by the dc component of an asymmetrical
external fault current.

4.3.

Trip Circuit

The main contacts will safely close 30 amperes at
250 volts dc and the seal-in contacts of the indicating
contactor switch will safely carry this current long
enough to trip a circuit breaker.

The indicating instantaneous trip contacts will safely
close 30 amperes at 250 volts dc and will carry this
current long enough to trip breaker.

The indicating contactor switch has two taps that pro-
vide a pick-up setting of 0.2 or 2 amperes. To change
taps requires connecting the lead located in front of
the tap block to the desired setting by means of a
screw connection.

4.4.

Trip Circuit Constants

Indicating Contactor Switch (ICS)

0.2 ampere tap

6.5 ohms dc resistance

2.0 ampere tap

0.15 ohms dc resistance

Sub 5

187A425

Figure 9:  External Schematic of the Type CA-16 Relays 

for Protection of a Six Circuit Bus with Three 
Feeder Groups.

Courtesy of NationalSwitchgear.com

Содержание CA-16

Страница 1: ...nt transformer accuracy class C voltage Iext maximum external fault current in secondary RMS amperes let Iext 100 if max external fault current is less than 100A Rs current transformer secondary wind...

Страница 2: ...41 337 3L 2 Photo Figure 1 Types CA 16 Relay front view Photo Figure 2 Types CA 16 Relay rear view Courtesy of NationalSwitchgear com...

Страница 3: ...se fluxes cause a contact opening torque 2 2 Operating Circuit The operating circuit consists of an auto transformer and an operating element The primary of the auto transformer which is the whole win...

Страница 4: ...fastened to the bottom of the guide rod by two small nuts Its position determines the pick up current of the ele ment The auto transformer is designed to saturate at high values of current to limit t...

Страница 5: ...ent transformers connected to the bus and the oper ating circuit is energized in accordance with the current flowing in the differential connection of the current transformers A current of 5 amperes i...

Страница 6: ...es of the current transformers involved The time of operation of the relays is shown in Figure 6 4 2 CA 26 Transformer Relay The type CA 26 transformer differential relay includes an indicating instan...

Страница 7: ...feeder ct s taking the precau tion that each feeder group has less than 14 amperes load current restraint coil continuous rating If the bus reduces to more than four circuits parallel ct s until only...

Страница 8: ...9 connections where there are more than three sources the source ct s should be paralleled to reduce the effective number of source connections to three The four circuit bus connections of Figure 8 ar...

Страница 9: ...of the four mounting holes on the flange for semi flush mounting or by means of the rear mounting stud or studs for projection mount ing Either a mounting stud or the mounting screws may be utilized f...

Страница 10: ...acts and target indication should occur at approximately the same instant Position the stationary contact for a minimum of 1 32 inch wipe The bridging moving contact should touch both stationary conta...

Страница 11: ...ve Fault Detector Loosen the lock nut at the top of the element and run the core screw down until it is flush with the top of the lock nut Back off the Micarta disc by loosening the two lock nuts Appl...

Страница 12: ...41 337 3L 12 Sub 2 408C507 Figure 14 External Schematic of the Type CA 26 Relay for Wye Wye Delta Transformer Protection Sub 2 408C507 Courtesy of NationalSwitchgear com...

Страница 13: ...41 337 3L 13 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Страница 14: ...41 337 3L 14 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Страница 15: ...41 337 3L 15 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Страница 16: ...ral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 visit our website at www abbus com papd Sub 16 57D7903 Figure 15 Outline and Drilling for the CA 16 and CA 26 Relays in FT...

Отзывы: