41-337.3L

4

gap fluxes cause a contact closing torque.

2.3.

Sensitive Fault Detector Circuit

 – when used

The sensitive fault detector circuit consists of an
auto-transformer and a contactor switch. The contac-
tor switch is connected across the secondary (tapped
section) of the auto-transformer winding.

The contactor switch is a small solenoid type ele-
ment. A cylindrical plunger rides up and down on a
vertical guide rod in the center of the solenoid coil.
The guide rod is fastened to the stationary core. The
guide rod is fastened to the stationary core, which in
turn screws into the unit frame. A silver disc is fas-
tened to the moving plunger through a helical spring.
When the coil is energized, the plunger moves
upward carrying the silver disc which bridges three
conical-shaped stationary contacts. In this position,
the helical spring is compressed and the plunger is
free to move while the contact remains stationary.
Thus, ac vibrations of the plunger are prevented from
causing contact bouncing. A Micarta disc is fastened

to the bottom of the guide rod by two small nuts. Its

position determines the pick up current of the ele-

ment.

The auto-transformer is designed to saturate at high

values of current to limit the amount of current to the

contactor switch.

2.4.

Indicating Contactor Switch Unit (ICS)

The dc indicating contactor switch is a small clapper

type device. A magnetic armature, to which leaf-

spring mounted contacts are attached, is attracted to

the magnetic core upon energization of the switch.

When the switch closes, the moving contacts bridge

two stationary contacts, completing the trip circuit.

Also during this operation two fingers on the arma-

ture deflect a spring located on the front of the

switch, which allows the operation indicator target to

drop. The target is reset from the outside of the case

by a push rod located at the bottom of the cover.

The front spring, in addition to holding the target, pro-

vides restraint for the armature and thus controls the

pick-up value of the switch.

Sub 2

187A434

Figure 5:  Internal Schematic of the Type CA-16 Bus 

Relay with a Sensitive Fault Detector.

Curve 537956

Figure 6:  Typical Time Curves of the CA-16 and CA-26 

differential Relays.

Courtesy of NationalSwitchgear.com

Содержание CA-16

Страница 1: ...nt transformer accuracy class C voltage Iext maximum external fault current in secondary RMS amperes let Iext 100 if max external fault current is less than 100A Rs current transformer secondary wind...

Страница 2: ...41 337 3L 2 Photo Figure 1 Types CA 16 Relay front view Photo Figure 2 Types CA 16 Relay rear view Courtesy of NationalSwitchgear com...

Страница 3: ...se fluxes cause a contact opening torque 2 2 Operating Circuit The operating circuit consists of an auto transformer and an operating element The primary of the auto transformer which is the whole win...

Страница 4: ...fastened to the bottom of the guide rod by two small nuts Its position determines the pick up current of the ele ment The auto transformer is designed to saturate at high values of current to limit t...

Страница 5: ...ent transformers connected to the bus and the oper ating circuit is energized in accordance with the current flowing in the differential connection of the current transformers A current of 5 amperes i...

Страница 6: ...es of the current transformers involved The time of operation of the relays is shown in Figure 6 4 2 CA 26 Transformer Relay The type CA 26 transformer differential relay includes an indicating instan...

Страница 7: ...feeder ct s taking the precau tion that each feeder group has less than 14 amperes load current restraint coil continuous rating If the bus reduces to more than four circuits parallel ct s until only...

Страница 8: ...9 connections where there are more than three sources the source ct s should be paralleled to reduce the effective number of source connections to three The four circuit bus connections of Figure 8 ar...

Страница 9: ...of the four mounting holes on the flange for semi flush mounting or by means of the rear mounting stud or studs for projection mount ing Either a mounting stud or the mounting screws may be utilized f...

Страница 10: ...acts and target indication should occur at approximately the same instant Position the stationary contact for a minimum of 1 32 inch wipe The bridging moving contact should touch both stationary conta...

Страница 11: ...ve Fault Detector Loosen the lock nut at the top of the element and run the core screw down until it is flush with the top of the lock nut Back off the Micarta disc by loosening the two lock nuts Appl...

Страница 12: ...41 337 3L 12 Sub 2 408C507 Figure 14 External Schematic of the Type CA 26 Relay for Wye Wye Delta Transformer Protection Sub 2 408C507 Courtesy of NationalSwitchgear com...

Страница 13: ...41 337 3L 13 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Страница 14: ...41 337 3L 14 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Страница 15: ...41 337 3L 15 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Страница 16: ...ral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 visit our website at www abbus com papd Sub 16 57D7903 Figure 15 Outline and Drilling for the CA 16 and CA 26 Relays in FT...

Отзывы: