2.5.

Indicating Instantaneous Trip Unit (IIT)

2.5.1. Fault Detector (FD) –

 when used

The instantaneous trip unit is a small ac operated
clapper type device. A magnetic armature, to which
leaf-spring mounted contacts are attached, is
attracted to the magnetic core upon energization of
the switch. When the switch closes, the moving con-
tacts bridge two stationary contacts, completing the
trip circuit. Also during this operation, (for the IIT
only) two fingers on the armature deflect a spring
located on the front of the switch which allows the
operation indicator target to drop. The target is reset
from the outside of the case by a push rod located at
the bottom of the cover.

A core screw accessible from the top of the switch
provides the adjustable pick-up range.

3. OPERATION

The types CA-16 and CA-26 relays are induction disc
relays with four electromagnets mounted on two
discs that are fastened on a common shaft. One of
the electromagnets is the operating element while
the other three are restraint elements. The restraint

elements are energized from the secondaries of cur-
rent transformers connected to the bus, and the oper-
ating circuit is energized in accordance with the
current flowing in the differential connection of the
current transformers.

A current of 5 amperes in a terminal 18 and out of
terminal 19 will produce a definite amount of restrain-
ing torque (see Figure 3). Similarly, a current of 5
amperes flowing in at terminal 16 and out of terminal
17 will produce an equal amount of torque. If both of
these currents flow at the same time with the polarity
as indicated above, their effect will be additive and
they will produce the same torque as through 10
amperes were flowing in terminal 16 and out of termi-
nal 17. Conversely, if equal currents flow in these two
coils, but in opposite directions, their ampere turns
will cancel and no torque will be produced. The same
relationship applies for the paired coils of the other
two restraining units of the relay. The restraint effect
will always be additive if currents flow in the coils
which belong to different restraint elements.

Curve 537957

Figure 7:  Typical Burden Characteristic of the Operating 

Circuit of the CA-16 and CA-26 Differential 
Relays.

Sub 5

187A424

Figure 8:  External Schematic of the Type CA-16 Relay for 

Three and Four Circuit Bus Protection.

Courtesy of NationalSwitchgear.com

Содержание CA-16

Страница 1: ...nt transformer accuracy class C voltage Iext maximum external fault current in secondary RMS amperes let Iext 100 if max external fault current is less than 100A Rs current transformer secondary wind...

Страница 2: ...41 337 3L 2 Photo Figure 1 Types CA 16 Relay front view Photo Figure 2 Types CA 16 Relay rear view Courtesy of NationalSwitchgear com...

Страница 3: ...se fluxes cause a contact opening torque 2 2 Operating Circuit The operating circuit consists of an auto transformer and an operating element The primary of the auto transformer which is the whole win...

Страница 4: ...fastened to the bottom of the guide rod by two small nuts Its position determines the pick up current of the ele ment The auto transformer is designed to saturate at high values of current to limit t...

Страница 5: ...ent transformers connected to the bus and the oper ating circuit is energized in accordance with the current flowing in the differential connection of the current transformers A current of 5 amperes i...

Страница 6: ...es of the current transformers involved The time of operation of the relays is shown in Figure 6 4 2 CA 26 Transformer Relay The type CA 26 transformer differential relay includes an indicating instan...

Страница 7: ...feeder ct s taking the precau tion that each feeder group has less than 14 amperes load current restraint coil continuous rating If the bus reduces to more than four circuits parallel ct s until only...

Страница 8: ...9 connections where there are more than three sources the source ct s should be paralleled to reduce the effective number of source connections to three The four circuit bus connections of Figure 8 ar...

Страница 9: ...of the four mounting holes on the flange for semi flush mounting or by means of the rear mounting stud or studs for projection mount ing Either a mounting stud or the mounting screws may be utilized f...

Страница 10: ...acts and target indication should occur at approximately the same instant Position the stationary contact for a minimum of 1 32 inch wipe The bridging moving contact should touch both stationary conta...

Страница 11: ...ve Fault Detector Loosen the lock nut at the top of the element and run the core screw down until it is flush with the top of the lock nut Back off the Micarta disc by loosening the two lock nuts Appl...

Страница 12: ...41 337 3L 12 Sub 2 408C507 Figure 14 External Schematic of the Type CA 26 Relay for Wye Wye Delta Transformer Protection Sub 2 408C507 Courtesy of NationalSwitchgear com...

Страница 13: ...41 337 3L 13 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Страница 14: ...41 337 3L 14 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Страница 15: ...41 337 3L 15 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Страница 16: ...ral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 visit our website at www abbus com papd Sub 16 57D7903 Figure 15 Outline and Drilling for the CA 16 and CA 26 Relays in FT...

Отзывы: