KNX Technical Reference Manual
Busch
-
priOn
®
42 | 0073-1-7388 | KNX Technical Reference Manual
Pos: 22.91 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/G - L/Lichtszenenaktor @ 9\mod_1269510610443_15.doc @ 53133 @ 2
Light scene actuator
Pos: 22.92 /KNX/Applikationsbeschreibungen/Applikationen - App/Lichtszenenaktor/App. - Lichtszenenaktor - DIN-A4 @ 9\mod_1269509871874_15.doc @ 53118 @
With the "Light scene actuator" application, it is possible to call up scenes that are stored in the device via the receipt of a
scene number on the 1-byte communication object "Scene call-up". A maximum of eight scenes with up to eight actuator
objects can be created.
For triggering different actuators, the size of the actuator groups communication objects can be set under the "Actuator
group type" parameter.
The user has the option of saving the scenes himself. A corresponding save telegram must be received for this (see the
description of the individual parameters).
Light scene actuator objects
No. Object
name
Data type
Flags
0
Light scene call-up (1 Byte)
1 Byte / DPT18.001
C, W, U
1…10
Actuator group A [B…J] (1-bit switching)
1 Bit EIS1 / DPT 1.001
C, W, T, U
1…10
Actuator group A [B…J] (1-bit Venetian blind)
1 Bit EIS7 / DPT 1.008
C, W, T, U
1…10
Actuator group A [B…J] (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, W, T, U
1…10
Actuator group A [B…J] (1-byte light scene number)
1 Byte / DPT 18.001
C, W, T, U
1…10
Actuator group A [B…J] (Temperature value absolute)
2 Byte EIS5 / DPT 9.001
C, W, T, U
10…19
Enable scene 1 [Scene 2 … Scene 10]
1 Bit EIS1 / DPT 1.001
C, W, T
Pos: 22.93 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/S - T/Sequenz @ 9\mod_1269511034750_15.doc @ 53143 @ 22
Sequence
Pos: 22.94 /KNX/Applikationsbeschreibungen/Applikationen - App/Sequenz/App. - Sequenz - DIN-A4 @ 9\mod_1269510677004_15.doc @ 53138 @
With the "Sequence " application it is possible to send out multiple telegrams with different values in a predefined sequence
consecutively over the same object.
In contrast to the scene, the "Sequence" application has only one communication object on which up to twelve individual
values are consecutively sent in twelve firmly set times. The times can be freely set from 1 s to 12 h. The "Sequence"
application lends itself to controlling showrooms for example.
The function can be temporarily blocked via an enable object.
Sequence objects
No. Object
name
Data type
Flags
0
Sequence value (1-bit switching)
1 Bit EIS1 / DPT 1.001
C, W, T, U
0
Sequence value (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, W, T, U
0
Sequence value (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W, T, U
0
Sequence value (1-byte light scene number)
1 Byte / DPT 18.001
C, W, T, U
0
Sequence value (2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, W, T, U
0
Sequence value (2 Byte Unsigned)
2 Byte EIS10 / DPT 7.001
C, W, T, U
1 Sequence
start
1 Bit EIS1 / DPT 1.001
C, W
2 Sequence
status
1 Bit EIS1 / DPT 1.001
C, T
4 Enable
1 Bit EIS1 / DPT 1.001
C, W
Pos: 22.95 /Spezial/Neues Layout 2010/Steuermodule_Neues_Layou+++++++++++ Seitenu+++++++++++ @ 9\mod_1268898668093_0.doc @ 52149 @