![ABB Busch-priOn Series Скачать руководство пользователя страница 39](http://html.mh-extra.com/html/abb/busch-prion-series/busch-prion-series_technical-reference-manual_2665039.webp)
KNX Technical Reference Manual | 0073-1-7388 | 39
Pos: 22.78 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/G - L/LED-Funktion @ 9\mod_1269508367126_15.doc @ 53030 @ 2
LED function
Pos: 22.79 /KNX/Applikationsbeschreibungen/Applikationen - App/LED Funktion/App. - LED-Funktion - DIN-A4 @ 9\mod_1269508113996_15.doc @ 53025 @
With the "LED function" application, the LED of the rocker can be used for orientation lighting, for status indication or for
function display. The LED can light up in different colours. The LED can also flash for alarm display and/or scene storage
display.
LED function objects
No. Object
name
Data type
Flags
0
Status (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, U
0
Status (1 Byte 0..100 %)
1 Bit EIS6 / DPT 5.001
C, W, U
1
Day / Night mode (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, U
2
Proximity (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, U
3 Alarm
(DPT_Alarm)
1 Bit / DPT_Alarm
C, W, U
4
Scene storage (DPT_Scene_Control)
1 Byte / DPT 18.001
C, W, U
Pos: 22.80 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/A - F/Alarmfunktion @ 9\mod_1269508521119_15.doc @ 53071 @ 2
Alarm function
Pos: 22.81 /KNX/Applikationsbeschreibungen/Applikationen - App/Alarmfunktion/App. - Alarmfunktion - DIN-A4 @ 9\mod_1269508449466_15.doc @ 53056 @
If the alarm function is switched active, the LED can be made to flash (1 Hz) during the status or function display via a 1-bit
"Alarm" communication object.
The LED will flash if an ON telegram is received on a 1-bit "Alarm" communication object. If the object receives an OFF
telegram, the LED will no longer flash.
The LED always flashes in the same colour and brightness that was specified via the status function or function display.
The alarm function could, for example, be used to display a wind alarm to the user to let the user know that no blind
operation is possible at that time. An additional application would be the signalling of an open door when the user would like
to lower a roller blind.
Hint:
If the LED is currently serving as an orientation light, it will not flash. This also applies if it is switched to orientation lighting
during flashing, i.e. the LED stops flashing immediately.
Pos: 22.82 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/S - T/Speicherfunktion Lichtszenen @ 9\mod_1269508749593_15.doc @ 53082 @ 22
Light scene memory function
Pos: 22.83 /KNX/Applikationsbeschreibungen/Applikationen - App/Speicherfunktion Lichtszenen/App. - Speicherfunktion Lichtszenen - DIN-A4 @ 9\mod_1269508652816_15.doc @ 53077 @
If the "Light scene memory function" is switched active, the LED can be made to flash (3 Hz) via a 1-bit communication
object "Scene storage" during the status or function display.
If a scene storage telegram is received on the 1-byte communication object "Scene storage", the LED will blink for 3 s and
then stop blinking automatically.
The LED always flashes in the same colour and brightness that is specified via the status function or function display.
Hint:
If the LED is currently serving as an orientation light, it will not blink. This also applies if orientation illumination is switched
to during flashing.
Pos: 22.84 /Spezial/Neues Layout 2010/Steuermodule_Neues_Layou+++++++++++ Seitenu+++++++++++ @ 9\mod_1268898668093_0.doc @ 52149 @