background image

0073-1-7388  

  Rev. 03  

  01.2011 

KNX Technical Reference Manual 

Busch

-

priOn

®

 

 

 

 

Pos: 2 /Produkthandbuch - DIN-A4/Titelblätter/Titelblatt - Busch-priOn @ 9\mod_1269242014078_15.doc @ 52250 @  

 

Busch-priOn

®

 

 

 

 

 

innovative and intuitive 

 

Improved control elements. For example, the new 8.9 cm 
(3.5”) TFT display as informative component of a flush-type 
combination is both stylish and efficient. Its menu can be 
individually adapted to every building and at all times 
provides an overview of the electrical consumers. From here 
the heating can be controlled, the lights dimmed or 
comprehensive scenes called up that trigger numerous 
preprogrammed actions. Meaningful symbols lead even the 
untrained user to his objective in just a few steps. The 
division of functions into individual areas such as light, 
heating or blinds, assists everyone to find his way around 
intuitively. Yet, this is not the end of possibilities for the 

Busch-priOn

® in classical building technology. The display 

can also be used for controlling music. 
 

 

The combination of pushbutton/rotary control element and 
display has a universal operating concept. The definition of 
a primary function makes its use particularly easy. The 
primary function appears when one approaches the display 
(a special proximity sensor is available) or when pressing 
the rotary control element. In principle, any switching, 
dimming, blinds, scene or sequence function that has been 
stored in the unit can be defined as primary function. It is 
only when the menu button is pressed that the display 
changes to the circuit menu. Up to 8 entries can be 
displayed via one symbol. By turning the pushbutton/rotary 
control element the user can bring the desired function into 
the foreground. An associated text below the focused 
symbol is shown (e.g. system settings, room control office, 
room control, living room, etc.). By activating the 
pushbutton/rotary control element the display changes to the 
respective list menu, which can consist of up to 15 different 
functions. The user can scroll through these functions by 
turning the pushbutton/rotary control element. The function 
is selected by pressing the button. 

 

 

=== Ende der Liste für Textmarke Cover === 

 

Содержание Busch-priOn Series

Страница 1: ...controlling music The combination of pushbutton rotary control element and display has a universal operating concept The definition of a primary function makes its use particularly easy The primary function appears when one approaches the display a special proximity sensor is available or when pressing the rotary control element In principle any switching dimming blinds scene or sequence function ...

Страница 2: ... Disconnect the mains power supply prior to mounting and or disassembly Failure to observe the installation and operating instructions may result in fire or other hazards Pos 4 4 Produkthandbuch DIN A4 Busch priOn Sicherheitshinweise Haftungsausschluss 16 mod_1292413036321_15 doc 97864 Disclaimer The content of this printed material has been checked for compliance with hardware and software Howeve...

Страница 3: ...6 3 Produkthandbuch DIN A4 Busch priOn Maßzeichnungen Maßzeichnungen_Best_Nr_ABB 15 mod_1289220462033_15 doc 96904 Flush type 8 9 cm 3 5 display with control element Busch priOn Flush type control element Busch priOn 6340 xxx 101 500 Flush type movement detector Busch priOn 6345 xxx 101 500 107 71 31 Support frame for Busch priOn 6346 12 101 500 Flush type rotary control element 6341 xxx 101 500 P...

Страница 4: ...re four choices of finish for the control elements studio white glass white glass black and stainless steel Most of the end strips are also available in these colour versions For the display style sheets there are three choices black blue and silver Modular design End strips These not only have a beautiful shape they optionally contain a temperature sensor for room temperature control an infrared ...

Страница 5: ...3 gang Top end strip IR proximity sensor 6350 825 101 500 Top end strip with display IR proximity sensor RTC 6351 825 101 500 Top end strip standard 6348 101 500 1 gang control element 6340 101 500 3 gang control element 6342 101 500 Rotary control element 6341 101 500 Movement detector 6345 101 500 8 9 cm display including control element 6344 101 500 Bottom end strip temperature 6352 101 500 Bot...

Страница 6: ...tector Page number Switching rocker total Page 21 Switching rocker left right Page 21 Dimming rocker total Page 21 Dimming rocker left right Page 22 Blind rocker total Page 22 Blind rocker left right Page 22 Value sender rocker total Page 23 Value sender rocker left right Page 23 Value sender 2 objects rocker left right Page 24 Value dimming sensor rocker total Page 24 Light scene extension unit w...

Страница 7: ...x value transducer Page 46 Threshold value hysteresis Page 47 PWM inverter Page 47 Priority Page 47 Pos 12 6 Produkthandbuch DIN A4 Busch priOn Kein gewöhnliches KNX Bedienelement Kein gewöhnliches KNX Bedienelement Abbildung 1 2fach 15 mod_1289223461875_15 doc 96952 Busch priOn Rotary control element Glass black Busch priOn 3 gang control element Glass black Busch priOn 1 gang control element Gla...

Страница 8: ... 15 15 7 22 16 16 0 16 1 Composed of display combinations plus 1 to 3 gang combinations without display with end strips Only one bus coupler is mounted behind every Busch priOn combination One standard bus coupler is adequate for one 1 gang support frame With the use of the 2 gang carrier frame the more powerful power bus coupler must be used The twisted pair version requires an external power pac...

Страница 9: ...mounted on top as well as below Its material can be different to that of the module The support frame is mounted by screwing it to the flush type bus coupler and for multiple combinations also to the wall Thanks to the anti fingerprint surface the stainless steel Busch priOn is easy to keep clean and maintains its sophisticated surface finish even when it is in use Glass surfaces and end strips ma...

Страница 10: ...8 7 Produkthandbuch DIN A4 Überschriften 3 Ebene Sollwerte 13 mod_1286269492130_15 doc 91520 22 Set values Pos 18 8 Spezial Neues Layout 2010 Steuermodule_Neues_Layout_2010 Wechsel von ein auf zweispaltig 9 mod_1268898451593_0 doc 52140 3 Pos 18 9 Produkthandbuch DIN A4 Busch triton Raumtemperaturregler Sollwerte 13 mod_1286269283224_15 doc 91495 Heating setpoint Cooling setpoint Temperature Tempe...

Страница 11: ... freely parameterized For example it can occur when an external temperature sensor no longer sends values Night setback The temperature can be reduced during the night This saves energy and makes the night s rest comfortable The heating starts again automatically the next morning to reach a comfortable temperature for rising Frost protection If parameterized frost protection will ensure that the t...

Страница 12: ...witchover to a different mode cannot take place in this case The frost heat protection must first be deactivated by closing an open window for example Night mode has the next highest priority followed by comfort mode If none of these three operating modes are active the room thermostat is in standby mode Pos 20 4 Produkthandbuch DIN A4 Busch triton Bedienung Betriebsartenumschaltung 1 Byte 13 mod_...

Страница 13: ...e measurement must be set on Internal and external The the temperature measured inside and outside can then be additionally weighted The setting for weighting depend on the local circumstances If the room thermostat and the additional measuring sensor are positioned equal distances from the heater in the case of panel heaters a 50 50 setting should provide good control results Pos 20 8 Produkthand...

Страница 14: ...her an object 1 channel two pipe system for heating and cooling or two objects 2 channels four pipe system for heating and cooling are to be displayed Separate control types can be configured each for heating and cooling One of the following control types can be selected 2 point PWM Continuous Fan coil The individual control types are described in greater detail in the following Pos 20 12 Produkth...

Страница 15: ... control value of 70 is to be issued at a pre set cycle time of 10 minutes the switch on time will be 7 minutes and the switch off time 3 minutes This transfers the advantages of the continuous control control at the desired setpoint no overshooting to drives which are designed only for On Off switching signals such as electrothermal drives To optimise the controlling characteristics of the heatin...

Страница 16: ...ton Bedienung Sollwerte 13 mod_1284722358805_15 doc 90094 33 Set values The room thermostat can operate with dependent or individual set values Both versions are explained in greater detail in the following Pos 20 21 Produkthandbuch DIN A4 Busch triton Bedienung Abhängige Sollwerte 13 mod_1284722436946_15 doc 90102 3232 Dependent setpoints In case of dependent setpoints there are two basic setpoin...

Страница 17: ... value must be sent to the corresponding communication object Setpoint heating comfort Setpoint heating standby Setpoint heating night mode Setpoint frost protection Setpoint cooling comfort Setpoint cooling standby Setpoint cooling night mode or Setpoint heat protection The values received are stored in the memory of the device and are retained in case of bus power failure and subsequent return o...

Страница 18: ...h is connected with a corresponding object of a fan coil actuator can be enabled This allows the fan coil room thermostat evaluate which fan stage is actually active on the fan coil actuator The display corresponds to the value of the communication object 0 OFF 1 stage 1 2 stage 2 3 stage 3 The parameter Evaluate operation status byte activates a 1 bit communication object Receive during operation...

Страница 19: ...ensation upper outside temperature value Summer compensation lower setpoint offset Summer compensation upper setpoint offset The value of the lower and upper temperature is used to specify from and to which temperature value a setpoint correction is to be made The lower and upper setpoint offset is used to specify by how many Kelvin the setpoint specified in the parameters or by the user via a man...

Страница 20: ...er setpoint offset The value of the lower and upper temperature is used to specify from and to which temperature value a setpoint correction is to be made The lower and upper setpoint offset is used to specify by how many Kelvin the setpoint specified in the parameters or by the user via a manual shift is to be adjusted during winter compensation Typical values for the winter compensation are 0 C ...

Страница 21: ...ate whether the rocker is actuated on the right or the left side In each case the application makes a separate set of parameters and communication objects available for the right and left side of the rocker The application enables a switching function to be implemented with one side of the rocker and to assign an additional button oriented function to the other side of the rocker Switching objects...

Страница 22: ...f the rocker switch that is assigned with the Blind rocker total application If a blind was lowered and halted at half height via a short button contact then a renewed long button contact will raise the blind Blind objects rocker total No Object name Data type Flags 0 Adjusting 1 Bit 1 Bit EIS7 DPT 1 008 C T 0 Adjusting 1 Byte 1 Byte EIS6 DPT 5 001 C T 1 Move 1 Bit 1 Bit EIS7 DPT 1 007 C T 1 Move ...

Страница 23: ...r Wippe Links Rechts 9 mod_1269425766812_15 doc 52735 22 Value sender rocker left right Pos 22 19 KNX Applikationsbeschreibungen Applikationen App Wert Taste App Wertsender Wippe Links Rechts DIN A4 9 mod_1269425575718_15 doc 52730 With the Value sender rocker left right application a telegram with a predefined value is sent out at an actuation or release of the rocker The Value sender rocker left...

Страница 24: ... Byte EIS9 DPT 14 xxx C W T U 0 Switching rising flank 4 Byte Signed 4 Byte EIS11 DPT 13 001 C W T U 0 Switching rising flank 4 Byte Unsigned 4 Byte EIS11 DPT 12 001 C W T U 1 Switching falling flank 1 Bit 1 Bit EIS1 DPT 1 001 C W T U 1 Switching falling flank 1 Byte 0 100 1 Byte EIS6 DPT 5 001 C W T U 1 Switching falling flank 1 Byte 0 255 1 Byte EIS14 DPT 5 010 C W T U 1 Switching falling flank ...

Страница 25: ...schalter Wippe Gesamt 9 mod_1269437200187_15 doc 52793 22 Step switch rocker total Pos 22 29 KNX Applikationsbeschreibungen Applikationen App Stufenschalter_Wippe_gesamt App Stufenschalter Wippe Gesamt DIN A4 9 mod_1269436921171_15 doc 52788 The application Step switch rocker total facilitates step type switching This means that the user can trigger different switching processes with each new oper...

Страница 26: ...33 Produkthandbuch DIN A4 Überschriften 2 Ebene M O Mehrfachbetätigung Wippe Links Rechts 9 mod_1269438670421_15 doc 52813 222 Multiple operation rocker left right Pos 22 34 KNX Applikationsbeschreibungen Applikationen App Mehrfachbetätigung_Wippe_links_rechts App Mehrfachbetätigung Wippe Links Rechts DIN A4 9 mod_1269437591625_15 doc 52808 With the Multiple operation rocker left right application...

Страница 27: ... 4 Byte EIS11 DPT 13 001 C W T 2 Switching 3 multiple operation 4 Byte Unsigned 4 Byte EIS11 DPT 12 001 C W T 3 Switching 4 multiple operation 1 Bit 1 Bit EIS1 DPT 1 001 C W T 3 Switching 4 multiple operation 1 Byte 0 100 1 Byte EIS6 DPT 5 001 C W T 3 Switching 4 multiple operation 1 Byte 0 255 1 Byte EIS14 DPT 5 010 C W T 3 Switching 4 multiple operation 2 Byte Float 2 Byte EIS5 DPT 9 xxx C W T 3...

Страница 28: ...Produkthandbuch DIN A4 Überschriften 2 Ebene P R RTR Betriebsart einstellen 9 mod_1269441295921_15 doc 52833 22 Setting RTC operation mode Pos 22 39 KNX Applikationsbeschreibungen Applikationen App RTR Betriebsart App RTR Betriebsart einstellen DIN A4 9 mod_1269441072468_15 doc 52828 With the Setting the RTC operation mode application an operation mode switchover for connected room temperature con...

Страница 29: ...ecial volume symbol is shown on the display which signals the user that a turn to the right increases the volume and a turn to the left reduces the volume A feedback signal from the connected actuator can not be shown here Depending on the function telegrams to the CD player control are sent out on the communication objects for CD on off CD selection CD play CD stop CD pause CD previous track CD n...

Страница 30: ...the desired station focus and call it up via a push button operation If the volume is to be regulated a special volume symbol is shown on the display which signals the user that a turn to the right increases the volume and a turn to the left reduces the volume A feedback signal from the connected actuator can not be shown here Depending on the function telegrams for radio control are sent out on t...

Страница 31: ... as receiver for the sent out telegrams Media control objects video player No Object name Data type Flags 0 Enable 1 Bit EIS1 DPT 1 001 C T U 1 Video On Off 1 Bit EIS1 DPT 1 001 C W T U 2 Video Play 1 Bit EIS1 DPT 1 001 C T 3 Video Stop 1 Bit EIS1 DPT 1 001 C T 4 Video Pause 1 Bit EIS1 DPT 1 001 C T 5 Video Forward Video Rewind 1 Bit EIS1 DPT 1 001 C T 6 Video Rewind Video Forward 1 Bit EIS1 DPT 1...

Страница 32: ...ed for each program This means that four switching times control times to those predefined values are sent out on the associated communication object Value For specifying the individual switching times the application uses the system time of the device The current time can be synchronized in the device settings via the 3 byte Time communication object see unit settings Weekly timer objects No Obje...

Страница 33: ...rameter Alarm clock objects No Object name Data type Flags 0 Acknowledgement 1 Bit EIS1 DPT 1 001 C W U 1 Snooze 1 Bit EIS1 DPT 1 001 C W U 2 Switching 1 bit switching 1 Bit EIS1 DPT 1 001 C T 2 Switching 1 bit moving 1 Bit EIS7 DPT 1 008 C T 2 Switching 1 Byte 0 100 1 Byte EIS6 DPT 5 001 C T 2 Switching scene call up 1 Byte DPT 18 001 C T 2 Switching 1 Byte 0 255 1 Byte EIS14 DPT 1 010 C T 2 Swit...

Страница 34: ...sages are active the message symbol with the highest priority is always shown Message objects No Object name Data type Flags 0 Message 1 Bit EIS1 DPT 1 001 C W U 1 Acknowledgement 1 Bit EIS1 DPT 1 001 C W T Pos 22 60 Produkthandbuch DIN A4 Überschriften 2 Ebene S T Text für Titel 9 mod_1269507114151_15 doc 52976 2 Title text Pos 22 61 KNX Applikationsbeschreibungen Applikationen App Text für Titel...

Страница 35: ...n App Sequenzaktoreinstellungen DIN A4 9 mod_1269507712999_15 doc 53014 With the Sequence actuator settings application and the press of the push button rotary control element it is possible to consecutively send out multiple telegrams with different values in a predefined sequence via the same object The representation of a sequence on the display is based on the representation of a scene In cont...

Страница 36: ... DPT 1 008 C R T 8 Position state 1 Byte EIS5 DPT 5 001 C R T 9 Slats position status 1 Byte EIS5 DPT 5 001 C R T Pos 22 72 Produkthandbuch DIN A4 Überschriften 2 Ebene S T Schaltaktorapplikation 10 mod_1269514683702_15 doc 53245 222 Switch actuator application Pos 22 73 KNX Applikationsbeschreibungen Applikationen App Schaltaktorapplikation App Schaltaktorapplikation DIN A4 10 mod_1269514450016_1...

Страница 37: ... on automatically when detecting a movement It switches off at the receipt of an OFF telegram on the External pushbutton input object The movement detector switches off automatically after 6 hours In the Automatic mode the movement detector switches on automatically when detecting a movement It switches off after the specified light on time beginning from the most recent detection or through the r...

Страница 38: ...IS 5 DPT 9 004 C W U 6 External brightness threshold 2 Byte EIS 5 DPT 9 004 C W U 7 Internal brightness threshold 1 Byte EIS 5 DPT 9 004 C W U 8 LED output 1 Bit EIS 1 DPT 1 001 C W U 9 Motion switching 1 Bit EIS 1 DPT 1 001 C T 9 Motion switching 1 Byte EIS 5 DPT 5 001 C T 9 Motion switching 1 Byte EIS 6 DPT 5 010 C T 10 Motion starting 1 Byte EIS 1 DPT 1 001 C T 11 Switchover of external pushbut...

Страница 39: ...ll no longer flash The LED always flashes in the same colour and brightness that was specified via the status function or function display The alarm function could for example be used to display a wind alarm to the user to let the user know that no blind operation is possible at that time An additional application would be the signalling of an open door when the user would like to lower a roller b...

Страница 40: ...255 1 Byte EIS14 DPT 5 010 C W 0 Input 2 Byte Float 2 Byte EIS5 DPT 9 xxx C W 0 Input 2 Byte Signed 2 Byte EIS10 DPT 8 001 C W 0 Input 2 Byte Unsigned 2 Byte EIS10 DPT 7 001 C W 0 Input 4 Byte Float 4 Byte EIS9 DPT 14 xxx C W 0 Input 4 Byte Signed 4 Byte EIS11 DPT 13 001 C W 0 Input 4 Byte Unsigned 4 Byte EIS11 DPT 12 001 C W 1 Output 1 Bit 1 Bit EIS1 DPT 1 001 C T 1 Output 1 Bit 1 Bit EIS7 DPT 1 ...

Страница 41: ...via the Input object the light on time is started immediately and a telegram with the same value of the telegram received on the input is sent out on the Output object This can be a light on time of 00 10 min to 88 45 min which is adjustable in 0 1 s steps After expiration of the light on time the Output object sends out an OFF telegram 1 bit or a telegram with the value 0 1 byte Via two additiona...

Страница 42: ...tor group A B J Temperature value absolute 2 Byte EIS5 DPT 9 001 C W T U 10 19 Enable scene 1 Scene 2 Scene 10 1 Bit EIS1 DPT 1 001 C W T Pos 22 93 Produkthandbuch DIN A4 Überschriften 2 Ebene S T Sequenz 9 mod_1269511034750_15 doc 53143 22 Sequence Pos 22 94 KNX Applikationsbeschreibungen Applikationen App Sequenz App Sequenz DIN A4 9 mod_1269510677004_15 doc 53138 With the Sequence application i...

Страница 43: ...e different applications The times for cyclic sending on the Output object are adjustable Via an additional Enable object there is the option of temporarily blocking the function Cyclic telegram objects No Object name Data type Flags 0 Input 1 bit switching 1 Bit EIS1 DPT 1 001 C W 0 Input 1 bit alarm 1 Bit EIS1 DPT 1 001 C W 0 Input 1 Byte 0 100 1 Byte EIS6 DPT 5 001 C W 0 Input 1 Byte 0 255 1 By...

Страница 44: ...ogik App Logik DIN A4 10 mod_1270534383703_15 doc 53453 Logic objects No Object name Data type Flags 0 Output 1 Bit 1 Bit EIS1 DPT 1 001 C W T 0 Output 1 Byte 1 Byte EIS14 DPT 5 010 C W T 1 Input 1 1 Bit 1 Bit EIS1 DPT 1 001 C W U 1 Input 1 1 Byte 1 Byte EIS14 DPT 5 010 C W U 2 Input 2 1 Bit 1 Bit EIS1 DPT 1 001 C W U 2 Input 2 1 Byte 1 Byte EIS14 DPT 5 010 C W U 3 Input 3 1 Bit 1 Bit EIS1 DPT 1 0...

Страница 45: ... control can occur from Input to output or also from Output to input provided the control input allows this Enabling via the control input can occur via an ON or an OFF telegram If for example the Control input setting is set to ON telegram only telegrams from the input are transmitted to the output if prior to this the control input has received an ON telegram It is also possible to block signals...

Страница 46: ...comparison of 4 byte floating point values physical values such as acceleration electrical current work etc 4 byte signed for the comparison of decimal values between 2 147 483 648 and 2 147 483 647 4 byte unsigned for the comparison of decimal values between 0 and 4 294 967 295 Hint With whole numbers the average value is rounded Min Max value transducer objects No Object name Data type Flags 0 O...

Страница 47: ...en Applikationen App PWM App PWM Umsetzer DIN A4 10 mod_1269513222290_15 doc 53209 With the PWM inverter application a 1 byte input signal can be converted to a 1 bit signal or a 1 byte signal via an equivalent pulse width modulation This function is required for instance if a room temperature controller issues a constant control value that controls a switching heating actuator for electrothermal ...

Страница 48: ...tiated Input priority has value 3 the value that is present on Switch input has no meaning The Output is switched to positively driven and has the value 1 Input priority has the value 2 The value that is present on Switch input has no meaning The Output is switched off positively driven and has the value 0 Input priority has the value 1 or 0 The Output is not positively driven The Switch input is ...

Страница 49: ...KNX Technical Reference Manual 0073 1 7388 49 ...

Страница 50: ...ll times make technical changes as well as changes to the contents of this document without prior notice The detailed specifications agreed to at the time of ordering apply to all orders ABB accepts no responsibility for possible errors or incompleteness in this document We reserve all rights to this document and the topics and illustrations contained therein The document and its contents or extra...

Отзывы: