Time
C
u
rr
e
n
t
activation_current
activation_time_ms
0
STATUS
Idle
Accumulating
Overload
(duration)
Idle
CONTROL
OUTPUT
OFF
OFF
ON
trip_duration_sec
Accumulated Charge <
trip_charge
trip_time_sec
GUID-8B4D7B83-F1F4-4D6E-AB17-BBF9AF5A520A V1 EN
Figure 18:
Overload caused by duration
4.6.2
Remote enabling and disabling of the load limiter
Once the load limiter functionality is enabled on the configuration file, it can be
remotely controlled by the protocol communication. The information object is
defined in the section [LOAD_LIMITER_CONTROL_SC].
•
0 = Disable load limiter
•
1 = Enable load limiter (if enabled on configuration file)
The issued value is not permanently stored and effects only until reboot or application
restart.
4.6.3
Load limiter status
The current status of the load limiter function is available for protocol communication.
The information object is defined in the section [LOAD_LIMITER_STATUS_DPI].
•
0 = Load limiter idle (waiting for the current to exceed the threshold)
•
1 = Load limiter disabled (does not monitor load)
•
2 = Loading detected, accumulating
•
3 = Overload, load disconnected
1MRS758459 C
Section 4
Functional description
ARC600
37
User Manual