30 - AKD-10: Key Interlock
The Emax 2 Retrofill circuit breakers provided as replacements for WavePro 800-
5000A
frame circuit breakers have a trip interlock feature which will function using
the
AKD-10 compartment mounted Key Interlock. A label is provided with full
instructions on
how to operate the Legacy Key Interlock. It is suggested to apply the label on the
inside of the compartment door. Following is a brief summary of how the Key
Interlock system is operated.
To activate the key interlock:
1. OPEN the breaker.
2. Rotate the screw on the lower front panel of the breaker which normally allows
access to the racking screw. This will hold the breaker trip free.
3. While the screw is held rotated Clockwise, the Key Interlock slide in the
switchgear is
pushed inward, elevating a pin on the left side of the breaker.
4. Turn the key to the key removal position, extending the bolt and lock the breaker in the
OPEN position
.