26
Alarm 1 Setpoint
Alarm 2 Setpoint
Press to advance
to next parameter
Press to advance
to next page
SECURITY CODE
0 0 0 0 0
or
SECURITY CODE
SECURITY CODE
%H2 IN AIR
%H2 IN CO2
AIR IN CO2
9.2
Range 1 Operating Page
Range 1 is selected for normal operations and the
Operating Page
indicates the purity of the hydrogen used as a coolant. The alarm
set points can be viewed but not altered. To change the alarm set points or program other parameters, refer to Section 10.
Hydrogen Purity
Shows the percentage of hydrogen in air.
These two keys are used to advance to all subsequent parameters and pages.
Alarm 1 Set Point
The set point value is programmmable – see Section 10.3,
Set Up Outputs Page
.
Alarm 2 Set Point
The set point value is programmmable – see Section 10.3,
Set Up Outputs Page
.
Advance to
Access to Secure Parameters
on page 28.
9.4
Range 3 Operating Page
Range 3 is selected only during purging and refilling operations and the
Operating Page
indicates the percentage of Air in the CO
2
or
Argon purge gas. Access to the programming pages is not possible with range 3 selected.
Purge Gas
Shows the percentage of Air in the CO
2
or Argon purge gas.
9.3
Range 2 Operating Page
Range 2 is selected only during purging and refilling operations and the
Operating Page
indicates the percentage of hydrogen in the
CO
2
or Argon purge gas. Access to the programming pages is not possible with range 2 selected.
Purge Gas
Shows the percentage of hydrogen in the CO
2
or Argon purge gas.
9
OPERATION…