8 Quick installation and start-up guide – ACSM1-204
Recommended wire sizes
Filter unit mains supply cable
DC cable
Tightening torques
Installing the control cables
Wiring the main contactor connection
Equip the installation with a main contactor that opens if the regen supply module
trips on a fault.
Regen supply module
frame size
Wire size
Wire size (AWG)
A
1.5 … 4 mm
2
15 … 12
B
2.5 … 6 mm
2
13 … 10
C
10 … 70 mm
2
7 … 2/0
D
25 … 70 mm
2
3 … 2/0
Regen supply module
frame size
Wire size
Wire size (AWG)
A
1.5 … 4 mm
2
15 … 12
B
4 … 6 mm
2
12 … 10
C
10 … 70 mm
2
7 … 2/0
D
35 … 70 mm
2
2 … 2/0
Regen supply module
frame size
Power terminals (supply and
braking resistor cables)
Screw lug
(Allen screw)
N·m (lbf·in)
N·m (lbf·ft)
A
0.5 … 0.6 (4.4 … 5.3)
N/A
B
1.2 … 1.5 (10.6 … 13.3)
N/A
C or D
3 (25)
15 (11)
Regen supply module
frame size
PE/Ground
terminals
Power cable
clamps
Power connector
covers
N·m (lbf·in)
N·m (lbf·in)
N·m (lbf·in)
A
1.5 (13)
1.5 (13)
N/A
B
1.5 (13)
1.5 (13)
N/A
C or D
3 (25)
1.5 (13)
3 (25)