Mechanical installation
Fasten the regen supply module to the mounting base using screws through the four
mounting holes. Frame A and B can be mounted onto a DIN rail, but it is
recommended to fasten the modules to the mounting base also by two screws
through the lower mounting holes.
Fasten the regen filter module as instructed in
WFU-xx Regen Filter Module
Installation Guide
.
Installing the power cables
Connection diagram
Connection procedure
Cabling examples are presented on page
. Tightening torques are presented on
page
and at appropriate points in the text. For power cable connections in an
installation example, see
on page
• Attach the terminal blocks included to the regen supply module.
•
Frame sizes C and D only
: Remove the two plastic connector covers at the top
and bottom of the regen supply module. Each cover is held by two screws.
• On IT (ungrounded) systems and corner-grounded TN systems, remove the
screw labeled VAR located close to the supply terminals. Also, remove the screws
ACSM1-204
PE
WFU-xx
L1 L2 L3
L1 L2 L3
U2 V2 W2 PE
U2 V2 W2 PE
U1 V1 W1
UDC+UDC-
R+ R-
M
~3
U1
V1 W1
PE
ACSM1-04
U2 V2 W2 PE
U1 V1 W1
UDC+UDC-
R+ R-
PE
1)
2)
4)
Input power line
No.
Description
1
Main disconnector and fuses (switch fuse)
2
Main contactor
3
DC fuses
4
Brake resistor (optional)
3)
3)
ACSM1-204 Quick Quide.book Page 5 Tuesday, October 6, 2009 11:02 AM