60 Planning the electrical installation
Motor cable shield
If the motor cable shield is used as the sole protective earth conductor of the motor,
make sure that the conductivity of the shield is sufficient. See
on page
or see IEC 61439-1.
To effectively suppress radiated and conducted radio-frequency emissions, the cable
shield conductivity must be at least 1/10 of the phase conductor conductivity. To meet
the requirements, use a copper or an aluminum shield. The figure shows the
minimum requirements for the motor cable shield. It has a concentric layer of copper
wires with an open helix of copper tape or copper wire. The better and tighter the
shield, the lower the emission level and bearing currents.
Additional US requirements
Use type MC continuous corrugated aluminum armor cable with symmetrical grounds
or shielded power cable for the motor cables if metallic conduit is not used. For the
North American market, 600 V AC cable is accepted for up to 500 V AC. A 1,000 V
AC cable is required above 500 V AC (below 600 V AC). The power cables must be
rated for 75 °C (167 °F).
Conduit
Couple separate parts of a conduit together: bridge the joints with a ground conductor
bonded to the conduit on each side of the joint. Also bond the conduits to the drive
enclosure and motor frame. Use separate conduits for input power, motor, brake
resistor, and control wiring. When conduit is used, type MC continuous corrugated
aluminum armor cable or shielded cable is not required. A dedicated ground cable is
always required.
Note
: Do not run motor wiring from more than one drive in the same conduit.
1
Sheath
2
Copper wire shield
3
Helix of copper tape or copper wire
4
Filling
5
Cable conductors
1
3
4
5
2
Содержание ACS880-M04
Страница 1: ...ABB machinery drives Hardware manual ACS880 M04 drive ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Safety instructions ...
Страница 28: ...28 About the manual ...
Страница 38: ...38 Operation principle and hardware description ...
Страница 48: ...48 Planning the cabinet installation ...
Страница 54: ...54 Mechanical installation ...
Страница 72: ...72 Planning the electrical installation ...
Страница 98: ...98 Electrical installation ...
Страница 102: ...102 Start up ...
Страница 108: ...108 Maintenance ...
Страница 140: ...140 Technical data ...
Страница 158: ...158 Mains chokes ...
Страница 164: ...164 EMC filters 7 Attach the terminal blocks to the filter 1 6 5 4 3 ...
Страница 166: ...166 EMC filters 6 Attach the terminal blocks to the filter 1 2 3 4 ...
Страница 168: ...168 EMC filters ...
Страница 182: ...Dimension drawings 182 Frame size R1 H1 H2 W D ...
Страница 183: ...Dimension drawings 183 Frame size R2 H2 H1 W D ...
Страница 184: ...Dimension drawings 184 Frame size R3 D W H1 H2 ...
Страница 185: ...Dimension drawings 185 Frame size R4 W H1 H2 D ...
Страница 187: ...187 Dimension drawings EMC filters type JFI x1 JFI A1 ...
Страница 188: ...Dimension drawings 188 JFI B1 ...
Страница 189: ...189 Dimension drawings EMC filters type JFI 0x ...
Страница 191: ...191 Dimension drawings Brake resistors type JBR xx ...
Страница 193: ...193 Dimension drawings ...
Страница 195: ...www abb com drives www abb com drivespartners 3AXD50000028613 Rev A EN 2016 04 11 Contact us ...