Supplying power for the auxiliary circuits
Power for the auxiliary circuits and cooling fans must be supplied externally, unless the
drive has an auxiliary voltage transformer (G344) and cooling fan transformer(s)
(G451).
The user must supply these options from external power sources:
•
+G300/+G301: Cabinet heaters and/or lighting
•
+G307: Connection for an external uninterruptible power supply
•
+G313: Power supply connection for a motor space heater output
For the voltages and fuse sizes, refer to the circuit diagrams delivered with the drive.
Using power factor compensation capacitors with the drive
Power factor compensation is not needed with AC drives. However, if a drive is to be
connected in a system with compensation capacitors installed, note the following restrictions.
WARNING!
Do not connect power factor compensation capacitors or harmonic filters to the
motor cables (between the drive and the motor). They are not meant to be used with
AC drives and can cause permanent damage to the drive or themselves.
If there are power factor compensation capacitors in parallel with the input of the drive:
1.
Do not connect a high-power capacitor to the power line while the drive is connected.
The connection will cause voltage transients that may trip or even damage the drive.
2.
If capacitor load is increased/decreased step by step when the AC drive is connected
to the power line, make sure that the connection steps are low enough not to cause
voltage transients that would trip the drive.
3.
Make sure that the power factor compensation unit is suitable for use in systems with
AC drives, ie, harmonic generating loads. In such systems, the compensation unit
should typically be equipped with a blocking reactor or harmonic filter.
Using a safety switch between the drive and the motor
ABB recommends to install a safety switch between the permanent magnet motor and the
drive output. The switch is needed to isolate the motor from the drive during maintenance
work on the drive.
Implementing the control of a contactor between drive and
motor
Implementing the control of the output contactor depends on the motor control mode and
stopping method selected.
When you select the DTC motor control mode and the motor ramp stop mode, use this
operation sequence to open the contactor:
1.
Give a stop command to the drive.
2.
Wait until the drive decelerates the motor to zero speed.
3.
Open the contactor.
Guidelines for planning the electrical installation 89
Содержание ACS880-37LC-0390A-7
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 37LC drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 13: ...16 Resistor braking Further information Table of contents 13 ...
Страница 14: ...14 ...
Страница 24: ...24 ...
Страница 28: ...28 ...
Страница 50: ...50 ...
Страница 70: ...70 Mechanical installation ...
Страница 110: ...10 110 Electrical installation ...
Страница 113: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 113 11 ...
Страница 134: ...134 ...
Страница 140: ...140 ...
Страница 148: ...a b c 148 Maintenance ...
Страница 151: ...4 5 6 Maintenance 151 ...
Страница 164: ...164 ...
Страница 174: ...174 ...
Страница 196: ...196 ...
Страница 199: ... Dimension drawing examples ACS880 37LC 0390A 7 with main contactor Dimensions 199 ...
Страница 201: ...ACS880 37LC 1270A 7 with common motor terminal cubicle Dimensions 201 ...
Страница 202: ...ACS880 37LC 1940A 7 with common motor terminal cubicle 202 Dimensions ...
Страница 205: ...Location and size of input terminals Contact ABB for details Dimensions 205 ...
Страница 206: ... 100 kA input cubicle option F274 206 Dimensions ...
Страница 208: ...Inverter module cubicle with two R8i modules bottom cable exit 208 Dimensions ...
Страница 209: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 209 ...
Страница 210: ...Brake chopper cubicle 210 Dimensions ...
Страница 211: ... Units with common motor terminal cubicle H359 Cubicle width 300 mm bottom cable exit Dimensions 211 ...
Страница 212: ...Cubicle width 300 mm top cable exit 212 Dimensions ...
Страница 213: ...Cubicle width 400 mm bottom cable exit Dimensions 213 ...
Страница 214: ...Cubicle width 400 mm top cable exit 214 Dimensions ...
Страница 215: ...Cubicle width 600 mm bottom cable exit Dimensions 215 ...
Страница 216: ...Cubicle width 600 mm top cable exit 216 Dimensions ...
Страница 238: ...238 ...
Страница 240: ...240 ...