The protective earth conductor must be sized as specified in Article 250.122 and table
250.122 of the National Electric Code, ANSI/NFPA 70.
For cord-connected equipment, it must not be possible to disconnect the protective earth
conductor before power is removed.
Selecting the control cables
■
Shielding
Only use shielded control cables.
Use a double-shielded twisted pair cable for analog signals. ABB recommends this type of
cable also for the pulse encoder signals. Use one individually shielded pair for each signal.
Do not use common return for different analog signals.
A double-shielded cable (a) is the best alternative for low-voltage digital signals, but
single-shielded (b) twisted pair cable is also acceptable.
a
b
■
Signals in separate cables
Run analog and digital signals in separate, shielded cables. Do not mix 24 V DC and
115/230 V AC signals in the same cable.
■
Signals that can be run in the same cable
If their voltage does not exceed 48 V, relay-controlled signals can be run in the same cables
as digital input signals. The relay-controlled signals should be run as twisted pairs.
■
Relay cable
The cable type with braided metallic shield (for example ÖLFLEX by LAPPKABEL, Germany)
has been tested and approved by ABB.
■
Control panel to drive cable
Use EIA-485, Cat 5e (or better) cable with male RJ-45 connectors. The maximum length of
the cable is 100 m (328 ft).
■
PC tool cable
Connect the Drive Composer PC tool to the drive through the USB port of the control panel.
Use a USB Type A (PC) - Type Mini-B (control panel) cable. The maximum length of the
cable is 3 m (9.8 ft).
Guidelines for planning the electrical installation 83
Содержание ACS880-37LC-0390A-7
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 37LC drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 13: ...16 Resistor braking Further information Table of contents 13 ...
Страница 14: ...14 ...
Страница 24: ...24 ...
Страница 28: ...28 ...
Страница 50: ...50 ...
Страница 70: ...70 Mechanical installation ...
Страница 110: ...10 110 Electrical installation ...
Страница 113: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 113 11 ...
Страница 134: ...134 ...
Страница 140: ...140 ...
Страница 148: ...a b c 148 Maintenance ...
Страница 151: ...4 5 6 Maintenance 151 ...
Страница 164: ...164 ...
Страница 174: ...174 ...
Страница 196: ...196 ...
Страница 199: ... Dimension drawing examples ACS880 37LC 0390A 7 with main contactor Dimensions 199 ...
Страница 201: ...ACS880 37LC 1270A 7 with common motor terminal cubicle Dimensions 201 ...
Страница 202: ...ACS880 37LC 1940A 7 with common motor terminal cubicle 202 Dimensions ...
Страница 205: ...Location and size of input terminals Contact ABB for details Dimensions 205 ...
Страница 206: ... 100 kA input cubicle option F274 206 Dimensions ...
Страница 208: ...Inverter module cubicle with two R8i modules bottom cable exit 208 Dimensions ...
Страница 209: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 209 ...
Страница 210: ...Brake chopper cubicle 210 Dimensions ...
Страница 211: ... Units with common motor terminal cubicle H359 Cubicle width 300 mm bottom cable exit Dimensions 211 ...
Страница 212: ...Cubicle width 300 mm top cable exit 212 Dimensions ...
Страница 213: ...Cubicle width 400 mm bottom cable exit Dimensions 213 ...
Страница 214: ...Cubicle width 400 mm top cable exit 214 Dimensions ...
Страница 215: ...Cubicle width 600 mm bottom cable exit Dimensions 215 ...
Страница 216: ...Cubicle width 600 mm top cable exit 216 Dimensions ...
Страница 238: ...238 ...
Страница 240: ...240 ...