82 Guidelines for planning the electrical installation
Use a double-shielded twisted pair cable for analog signals. This type of cable is
recommended for the pulse encoder signals also. Employ one individually shielded pair for
each signal. Do not use common return for different analog signals.
A double-shielded cable (figure a below) is the best alternative for low-voltage digital
signals but single-shielded (b) twisted pair cable is also acceptable.
Signals in separate cables
Run analog and digital signals in separate, shielded cables. Never mix 24 V DC and
115/230 V AC signals in the same cable.
Signals allowed to be run in the same cable
Relay-controlled signals, providing their voltage does not exceed 48 V, can be run in the
same cables as digital input signals. The relay-controlled signals should be run as twisted
pairs.
Relay cable type
The cable type with braided metallic screen (for example ÖLFLEX by LAPPKABEL,
Germany) has been tested and approved by ABB.
Control panel cable length and type
In remote use, the cable connecting the control panel to the drive must not be longer than
three meters (10 ft). Cable type: shielded CAT 5e or better Ethernet patch cable with RJ-45
ends.
Routing the cables
Route the motor cable away from other cable routes. Motor cables of several drives can be
run in parallel installed next to each other. The motor cable, input power cable and control
cables should be installed on separate trays. Avoid long parallel runs of motor cables with
other cables in order to decrease electromagnetic interference caused by the rapid
changes in the drive output voltage.
Where control cables must cross power cables, make sure they are arranged at an angle
as near to 90 degrees as possible. Do not run extra cables through the drive.
The cable trays must have good electrical bonding to each other and to the grounding
electrodes. Aluminum tray systems can be used to improve local equalizing of potential.
a
b
Содержание ACS880-17
Страница 1: ...ABB industrial drives Hardware manual ACS880 37 drives ...
Страница 3: ......
Страница 4: ......
Страница 6: ......
Страница 16: ...16 ...
Страница 30: ...30 Introduction to the manual ...
Страница 61: ...Mechanical installation 61 Moving the crate with a forklift Free width for fork tines 750 mm 29 5 ...
Страница 70: ...70 Mechanical installation ...
Страница 105: ...Electrical installation 105 4 5 3 6 7 ...
Страница 107: ...Electrical installation 107 5 6 4 3 ...
Страница 108: ...108 Electrical installation 7 8 8 ...
Страница 109: ...Electrical installation 109 9 10 ...
Страница 111: ...Electrical installation 111 2 360 grounding detail a b b 1 5 a 11 b a PE 10 7 5 6 8 ...
Страница 117: ...Electrical installation 117 PE 11 8 4 9 11 ...
Страница 134: ...134 Control units of the drive ...
Страница 140: ...140 Start up ...
Страница 142: ...142 Fault tracing ...
Страница 154: ...154 Maintenance 4 5 6 7 8 6 10 10 ...
Страница 162: ...162 Maintenance 5 6 3 4 7 ...
Страница 163: ...Maintenance 163 6 8 7 11 10 9 ...
Страница 167: ...Maintenance 167 3 4b 4a 4b 8 ...
Страница 185: ...Technical data 185 Declaration of Conformity ...
Страница 186: ...186 Technical data ...
Страница 196: ...196 Dimensions Dimension drawing examples Frame 1 R8i 1 R8i ...
Страница 197: ...Dimensions 197 Frame 1 R8i 1 R8i top cable entry exit H351 H353 ...
Страница 198: ...198 Dimensions Frame 1 R8i 1 R8i with brake choppers and resistors D150 D151 ...
Страница 199: ...Dimensions 199 Frame 1 R8i 1 R8i with sine output filter E206 ...
Страница 200: ...200 Dimensions Frame 2 R8i 2 R8i eg ACS880 37 1110A 3 IP22 ...
Страница 201: ...Dimensions 201 Frame 2 R8i 2 R8i eg ACS880 37 1210A 3 IP54 ...
Страница 202: ...202 Dimensions Frame 2 R8i 2 R8i with main breaker F255 and common motor terminal cubicle H359 1 2 ...
Страница 203: ...Dimensions 203 Frame 2 R8i 2 R8i with main breaker F255 and common motor terminal cubicle H359 2 2 ...
Страница 204: ...204 Dimensions Frame 2 R8i 2 R8i with main breaker F255 and top entry top exit H351 H353 1 2 ...
Страница 205: ...Dimensions 205 Frame 2 R8i 2 R8i with main breaker F255 and top entry top exit H351 H353 2 2 ...
Страница 206: ...206 Dimensions Frame 3 R8i 3 R8i 1 2 ...
Страница 207: ...Dimensions 207 Frame 3 R8i 3 R8i 2 2 ...
Страница 208: ...208 Dimensions Frame 3 R8i 3 R8i with common motor terminal cubicle H359 1 2 ...
Страница 209: ...Dimensions 209 Frame 3 R8i 3 R8i with common motor terminal cubicle H359 2 2 ...
Страница 213: ...Dimensions 213 Units with main breaker 600 mm bottom cable entry Units with main breaker 600 mm top cable entry ...
Страница 217: ...Dimensions 217 Sine filter E206 cubicle 1000 mm top cable exit ...
Страница 219: ...Dimensions 219 Cubicle width 300 mm double busbar version bottom cable exit Cubicle width 300 mm top cable exit ...
Страница 220: ...220 Dimensions Cubicle width 300 mm double busbar version top cable exit Cubicle width 400 mm bottom cable exit ...
Страница 221: ...Dimensions 221 Cubicle width 400 mm top cable exit Cubicle width 600 mm bottom cable exit ...
Страница 222: ...222 Dimensions Cubicle width 600 mm top cable exit ...
Страница 234: ...234 The Safe torque off function ...
Страница 244: ...www abb com drives www abb com drivespartners 3AXD50000020437 Rev A EN 2015 02 06 Contact us ...