Measuring the insulation
■
Measuring the insulation of the drive
WARNING!
Do not do any voltage withstand or insulation resistance tests on any part of the
drive as testing can damage the drive. Every drive has been tested for insulation
between the main circuit and the chassis at the factory. Also, there are
voltage-limiting circuits inside the drive which cut down the testing voltage
automatically.
■
Measuring the insulation of the input power cable
Before you connect the input power cable to the drive, measure its insulation according to
local regulations.
■
Measuring the insulation of the motor and motor cable
WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or death,
or damage to the equipment can occur. If you are not a qualified electrical
professional, do not do installation or maintenance work.
1. Do the steps in section
Electrical safety precautions (page 18)
before you start the work.
2. Make sure that the motor cable is disconnected from the drive output terminals.
3. Measure the insulation resistance between each phase conductor and the protective
earth conductor. Use a measuring voltage of 1000 V DC. The insulation resistance of
an ABB motor must be more than 100 Mohm (reference value at 25 C [77°F]). For the
insulation resistance of other motors, refer to the manufacturer’s instructions.
Note:
Moisture inside the motor casing reduces the insulation resistance. If you think
that there is moisture in the motor, dry the motor and do the measurement again.
1000 V DC,
> 100 Mohm
U1-PE, V1-PE, W1-PE
M
3~
U1
V1
W1
PE
ohm
Grounding system compatibility check
The standard drive with no EMC filter or with EMC E210 and the ground-to-phase
varistors connected can be installed to a symmetrically grounded TN-S system. If you install
the drive to another system, you may need to disconnect the EMC filter and ground-to-phase
varistors. See
ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor
disconnecting instructions
[English].
100 Electrical installation
Содержание ACS880-14
Страница 1: ...ABB INDUSTRIAL DRIVES ACS880 14 drive modules 132 400 kW 200 400 hp Hardware manual...
Страница 2: ......
Страница 4: ......
Страница 14: ...14...
Страница 24: ...24...
Страница 30: ...30...
Страница 54: ...54...
Страница 64: ...64...
Страница 98: ...98...
Страница 114: ...With twin connectors in the control panel holder 1 2 3 1 114 Electrical installation...
Страница 115: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 115 11...
Страница 142: ...4 5 6 3 3 1 1 1 1 2 142 Installation example with full cabling panels option H381...
Страница 150: ...150 Installation example with full cabling panels option H381...
Страница 156: ...156...
Страница 204: ...Standard configuration 204 Dimension drawings...
Страница 205: ...Location of power cable connection terminals with options H370 H356 3AXD50000038012 Dimension drawings 205...
Страница 206: ...Drive module with options 0B051 H356 0H371 206 Dimension drawings...
Страница 207: ...Configuration with option H381 3AXD50000323210 Dimension drawings 207...
Страница 208: ...LCL filter module 208 Dimension drawings...
Страница 212: ...External control unit 3AXD50000011687 212 Dimension drawings...
Страница 230: ...Declaration of conformity 230 The Safe torque off function...
Страница 236: ...Combi screw M8 30 Hex 20 N m 14 75 lbf ft Tapping screw M6 12 Torx T30 Hex 8 N m 71 lbf in 8 10 9 11 12 236...
Страница 241: ...241...
Страница 246: ...246...