One-channel digital input
1
2
3
4
5
Customer motor sensor(s)
1
Customer protection relay(s)
2
FSO module
3
FSE module (optional)
4
Drive STO
5
Two-channel digital input
1
2
3
4
5
Customer motor sensor(s)
1
Customer protection relay(s)
2
FSO module
3
FSE module (optional)
4
Drive STO
5
■
Response times
The response time of the Safe disconnection (STO) function is < 50 ms for all ACS880
drives. For the exact response times for each drive/inverter module type, see the drive/inverter
module hardware manual.
When the function contains the FSO module, the response time of the Safe disconnection
function is < 100 ms.