Description
Example value
Name
Index
Sets the power-up acknowledgement method of the
FSO module.
Automatic
Power-up acknow-
ledgement
FSOGEN.41
Automatic
: You do not need to push a reset button after
switching on the FSO module. The FSO module gener-
ates the acknowledgement signal automatically after
the power-up.
Manual
: The FSO module reads the external acknow-
ledgement signal through the digital input defined by
parameter
.
Make sure that the value is
Automatic
.
Sets the digital input for the acknowledgement signal
when parameter
has value
Manual
.
None or eg.
DI X113:2
Acknowledgement
button input
FSOGEN.42
None
: No acknowledgement signal connected/required
(parameter
has value
Automatic
).
DI X113:2
: The acknowledgement signal (reset circuit)
is connected to this digital input.
In the safety function described in this manual, you can
use this parameter to implement a manual reset in the
FSO module.
Sets the general zero speed limit for safety functions
when no safety encoder is in use.
90.0 rpm
Zero speed without
encoder
FSOGEN.51
STO function: The value has no effect.
SS1 function: The FSO module activates the drive STO
function when the drive has decelerated the motor
speed below this value. Adjust the default value accord-
ing to application requirements.
Sets the general zero speed limit for safety functions
when a safety encoder is in use.
0.0 rpm
Zero speed with en-
coder
FSOGEN.52
STO function: The drive STO function is active (cannot
be reset) until the motor speed is less than or equal to
this value.
SS1 function: The FSO module activates the drive STO
function when the drive has decelerated the motor
speed to less than this value. Adjust the default value
according to application requirements.
Note:
This parameter is used only with FSO-21 and
when a safety encoder is used in the application.
Sets the type of the event that the FSO module gener-
ates and sends to the drive after external requests that
end to a successful activation of the drive STO function
(STO, SSE or SS1).
Warning
STO indication ext
request
FSOGEN.61
None, Warning, Event
: You do not have to reset the
drive/inverter unit.
Fault
: You have to reset the drive/inverter unit.
In the safety functions described in this manual, you
can use this indication as the motor overtemperature
indication message and to implement a manual reset.
Adjust the default value when necessary.
28 Parameter settings