Make sure that at least one of these indications generates a fault if:
•
the protection relay does not contain a manual reset, and
•
the FSO module is not configured for an STO manual reset.
■
Connection diagram (two-channel connection)
The diagram below shows the wiring of the two-channel connection. The system integrator
must get the components and do the installations drawn outside the drive border line.
3
24 … 240 V AC / DC
XSTO 1
2
3
4
1 2 3 4 1 2
24 V / 1 A
X111 X112
X1
10
X1
12
1 2 3 4 …10
1 2 3 4 …10
X113
X114
1
2
3
4
3~
Ex M
5
Drive
1
FSO module
2
ATEX-compliant protection relay. The relay monitors a sensor circuit, and de-energizes the FSO module
input by opening the control circuits when necessary.
3
Motor temperature sensor
4
Potentially explosive atmosphere
5
Implementing a motor thermal protection circuit 21