Electrical installation 77
Connection procedure – cable glands at the cable lead-through
For description of the cable glands, see chapter
Operation principle and hardware
, page
WARNING!
Read and follow the instructions given in chapter
.
Ignoring the instructions can cause physical injury or death, or damage to the
equipment.
1. Open the door of the inverter module cubicle.
2. Remove the shroud that protects the rotor cable connection busbars and cable
entries.
3. Remove the fans (see the pictures below). Undo the two fastening screws of the fan
collar, push the collar a bit inwards and pull the fan with collar out.
4. When shielded cable is used:
Lead the cables into the inside of the cubicle. Ground a shielded cable 360° at the
lead-through with an EMC cable gland.
•
Connect the cables as follows:
•
Cut the cables to suitable length. Strip the cables and conductors. Fasten the
cable lugs to the conductor ends.
•
Twist the cable shields into bundles and connect to cabinet PE (ground) busbar.
Connect any separate ground conductors or cables to cabinet PE (ground)
busbar.
•
Connect the phase conductors to terminals U2, V2 and W2. See the appropriate
connection diagram above. Tighten the phase conductors and PE to 70 N·m
(50 lbf·ft) torque.
When single-core cables without metal shield are used:
•
Lead the cables into the inside of the cubicle through the IP sealing glands.
•
Connect the phase conductors to terminals U2, V2 and W2, and the PE
conductors to the PE terminal. See the appropriate connection diagram above.
Tighten the phase and PE conductors to 70 N·m (50 lbf·ft) torque.
5. Provide support for the cables whenever necessary.
6. Install the fans removed earlier.
7. Refit the shroud removed earlier and close the door.
8. Connect the generator end of the cable. See the diagrams above and the drawings
below. For minimum radio frequency interference and generator bearing current
ground the cable shield 360° at the lead-through of the generator terminal box, or
ground the cable by twisting the shield as follows: flattened width > 1/5 × length. For
the generator specific instructions, see the manufacturer’s user manual.
Содержание ACS800-67LC
Страница 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 22: ...22 Introduction to the manual ...
Страница 42: ...42 Operation principle and hardware description ...
Страница 52: ...52 Mechanical installation ...
Страница 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Страница 92: ...92 Maintenance 4 6 5 5 ...
Страница 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Страница 109: ...Maintenance 109 5 6 7 ...
Страница 131: ...Technical data 131 Declaration of incorporation ...
Страница 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Страница 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Страница 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Страница 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Страница 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Страница 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Страница 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Страница 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Страница 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Страница 147: ...Dimension drawings 147 Option 2H372 ...
Страница 148: ...148 Dimension drawings Option 3H372 ...
Страница 149: ...Dimension drawings 149 Option 1H373 ...
Страница 150: ...150 Dimension drawings Option 2H373 ...
Страница 151: ...Dimension drawings 151 Option 3H373 ...
Страница 152: ...152 Dimension drawings Option H375 ...