Electrical installation
64
360 degrees grounding
When the outer surface of the shield is covered with non-conductive material
• Strip the cable carefully (do not cut the grounding wire and the shield)
• Turn the shield inside out to expose the conductive surface.
• Wrap the grounding wire around the conductive surface.
• Slide a conductive clamp onto the conductive part.
• Fasten the clamp to the grounding plate with a screw as close as possible to the
terminals where the wires are about to be connected.
Connecting the shield wires
Single-shielded cables: Twist the grounding wires of the outer shield and connect
them through the shortest possible route to the nearest grounding hole with a cable
lug and a screw. Double-shielded cables: Connect each pair cable shield (twisted
grounding wires) with other pair cable shields of the same cable to the nearest
grounding hole with a cable lug and a screw.
Do not connect shields of different cables to the same cable lug and grounding
screw.
Leave the other end of the shield unconnected or ground it indirectly via a few
nanofarads high-frequency capacitor (e.g. 3.3 nF / 630 V). The shield can also be
grounded directly at both ends if they are
in the same ground line
with no significant
voltage drop between the end points.
Keep the signal wire pairs twisted as close to the terminals as possible. Twisting the
wire with its return wire reduces disturbances caused by inductive coupling.
1
2
3 4
Insulation
Double-shielded cable
Single-shielded cable
Содержание ACS800-11
Страница 1: ...ACS800 Hardware Manual ACS800 11 Drives 5 5 to 110 kW ACS800 U11 Drives 7 5 to 125 HP ...
Страница 4: ......
Страница 12: ...Safety instructions 12 ...
Страница 30: ...The ACS800 11 U11 30 ...
Страница 36: ...Mechanical installation 36 ...
Страница 54: ...Planning the electrical installation 54 ...
Страница 59: ...Electrical installation 59 1 2 3 Views of frame size R5 U1 V1 W1 V2 W2 U2 UDC UDC 5 5 PE 6 6 8 9 9 ...
Страница 74: ...Installation checklist 74 ...
Страница 84: ...Operation 84 ...
Страница 104: ...Technical data 102 ...
Страница 105: ...Dimensional drawings 103 Dimensional drawings The dimensions are given in millimetres and inches ...
Страница 108: ...Dimensional drawings 106 ...
Страница 111: ...External 24 V power supply for the RMIO board 109 5 6 7 8 ...
Страница 112: ...External 24 V power supply for the RMIO board 110 ...
Страница 113: ......