422 Fieldbus control through the embedded fieldbus interface (EFB)
Coils (0xxxx reference set)
Coils are 1-bit read/write values. Control Word bits are exposed with this data type.
The table below summarizes the Modbus coils (0xxxx reference set). Note that the
references are 1-based index which match the address transmitted on the wire.
Reference ABB Drives profile
DCU Profile
000001
OFF1_CONTROL
STOP
000002
OFF2_CONTROL
START
000003
OFF3_CONTROL
Reserved
000004
INHIBIT_OPERATION
Reserved
000005
RAMP_OUT_ZERO
RESET
000006
RAMP_HOLD
EXT2
000007
RAMP_IN_ZERO
RUN_DISABLE
000008
RESET
STOPMODE_RAMP
000009
JOGGING_1
STOPMODE_EMERGENCY_RAMP
000010
JOGGING_2
STOPMODE_COAST
000011
REMOTE_CMD
Reserved
000012
EXT_CTRL_LOC
RAMP_OUT_ZERO
000013
USER_0
RAMP_HOLD
000014
USER_1
RAMP_IN_ZERO
000015
USER_2
Reserved
000016
USER_3
Reserved
000017
Reserved
FB_LOCAL_CTL
000018
Reserved
FB_LOCAL_REF
000019
Reserved
Reserved
000020
Reserved
Reserved
000021
Reserved
Reserved
000022
Reserved
Reserved
000023
Reserved
USER_0
000024
Reserved
USER_1
000025
Reserved
USER_2
000026
Reserved
USER_3
000027
Reserved
Reserved
000028
Reserved
Reserved
000029
Reserved
Reserved
000030
Reserved
Reserved
000031
Reserved
Reserved
000032
Reserved
Reserved
ACS580 FW.book Page 422 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...