174 Parameters
AO has automatic scaling. Every time the source for the AO is changed, the scaling range is
changed accordingly. User given minimum and maximum values override the automatic values.
-32768.0…32767.0
Real signal value corresponding to minimum AO1 output
value.
1 = 1
Defines the real maximum value of the signal (selected by
parameter
) that corresponds to the
maximum required AO1 output value (defined by parameter
). See parameter
50.0
-32768.0…32767.0
Real signal value corresponding to maximum AO1 output
value.
1 = 1
Defines the minimum output value for analog output AO1.
See also drawing at parameter
.
0.000 mA
0.000…22.000 mA /
0.000…11.000 V
Minimum AO1 output value.
1000 = 1 mA
Defines the maximum output value for analog output AO1.
See also drawing at parameter
.
20.000 mA
0.000…22.000 mA /
0.000…11.000 V
Maximum AO1 output value.
1000 = 1 mA
No.
Name/Value
Description
Def/FbEq16
,
,
N/A (Output is constant zero.)
0
0
0
Motor current % of motor
nominal
0%
100%
0
Min. value of
Max. value of
0
0
0
0
0
Min. value of
Max. value of
N/A (Analog output is not scaled; it is determined by the
sensor’s triggering voltage.)
0
0
0
0
0
0
Min. value of
Max. value of
Min. value of the selected
parameter
Max. value of the selected
parameter
ACS580 FW.book Page 174 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...