05 MECHANICAL INSTALLATION
3BHS799208 E01 REV E
ACS5000 WATER-COOLED
USER MANUAL
78/186
5.8
Applying silicone
Silicone prevents water from entering the gap between two joining roof
plates. Apply silicone where two transport units have been joined
(Fig. 5-3). Gaps within a transport unit are factory-sealed.
Figure 5-3 Applying silicone
5.9
Installing roof joints
Install the roof joints across shipping splits at the following locations:
• Marine drives: at the front of the roof (the back is reserved for roof
attachments, see “5.11 Installing roof attachments” on page 84.)
• Standard drives: at the front and the back of the roof
Note:
For the exact number and fitting location of roof joints, see
“Appendix C – Mechanical drawings”.
Figure 5-4 Roof joint
Table 5-1 Installation material per roof joint
Items
Details
ID Number
Connecting piece
8 x 80 x 220 mm
3BHB011552R0001
Hex-head bolt
M16 x 40
NB 312350P0464
Washer
17x30x3
9ABA450078P0008