3BHS799208 E01 REV E
ACS5000 WATER-COOLED
USER MANUAL
131/186
08 OPERATION
If a fault cannot be reset, it must be rectified by the
responsible personnel.
When no alarms and faults are present and the drive is ready, the CDP
control panel displays ReadyOn.
4.
Press the SUPPLY ON pushbutton on the control compartment door
to charge the DC link. The pushbutton flashes during charging.
The status line of the CDP control panel alternates between Charging
and AuxiliaryOn.
After charging has been finished, the following takes place:
• The main circuit breaker closes automatically.
• The SUPPLY ON pushbutton lights up permanently.
5.
Enter the reference value.
Note:
For more information, see “9.3.2 Entering a reference value”
1 L ->
0.0 rpm
StateINU
ReadyOn
MOTOR SP
0.00 rpm
POWER
0.0 kW
1 L ->
0.0 rpm
StateINU
Charging
MOTOR SP
0.00 rpm
POWER
0.0 kW
Alternating display message:
• Charging
• AuxiliaryOn
1 L -> 0.0 rpm 0
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
1 L -> [600.0 rpm] 0
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW