8.6.1
Start sequence of the drive
1) NotReadyOn
2) ReadyOn
• Auxiliary power supply on
• PCU doors closed and locked
• Drive not grounded
• No emergency-off
• No fault
• WCU ready
3) On command
4) Charging
• DC link charges
• MCB closes
• Cooling system switches on
5) ReadyRun
6) Start Command
• Inverter starts to modulate
7) ReadyRef
8) Operation