Actual signals and parameters 229
SPD COMP
REV
Speed compensation is used for constant distance braking if
the direction of rotation is reverse. Speed difference
(between used speed and maximum speed) is
compensated by running the drive with current speed before
the motor is stopped along a ramp. See section
Acceleration and deceleration ramps
on page
.
If the direction of rotation is forward, the drive is stopped
along a ramp.
5
2103 DC MAGN
TIME
Defines the pre-magnetizing time. See parameter
. After the start command, the drive
automatically pre-magnetizes the motor for the defined time.
0.30 s
0.00…10.00 s
Magnetizing time. Set this value long enough to allow full
motor magnetization. Too long a time heats the motor
excessively.
1 = 0.01 s
2104 DC HOLD CTL Activates the DC hold or DC braking function.
NOT SEL
Inactive
0
DC HOLD
DC hold function active. DC hold is not possible if parameter
When both the reference and the motor speed drop below
the value of parameter
, the drive
will stop generating sinusoidal current and start to inject DC
into the motor. The current is set by parameter
. When the reference speed exceeds parameter
value, normal drive operation continues.
Note:
DC hold has no effect if the start signal is switched
off.
Note:
Injecting DC current into the motor causes the motor
to heat up. In applications where long DC hold times are
required, externally ventilated motors should be used. If the
DC hold period is long, the DC hold cannot prevent the
motor shaft from rotating if a constant load is applied to the
motor.
1
All parameters
No.
Name/Value
Description
Def/FbEq
t
t
Motor speed
DC hold speed
Ref
DC hold
Содержание ACS355 series
Страница 1: ...ABB machinery drives User s manual ACS355 drives ...
Страница 4: ......
Страница 16: ...16 ...
Страница 32: ...32 Operation principle and hardware description ...
Страница 58: ...58 Electrical installation ...
Страница 74: ...74 Start up control with I O and ID run ...
Страница 106: ...106 Control panels ...
Страница 120: ...120 Application macros ...
Страница 178: ...178 Program features ...
Страница 338: ...338 Fieldbus control with embedded fieldbus ...
Страница 368: ...368 Fault tracing ...
Страница 404: ...404 Dimension drawings ...
Страница 410: ...410 Appendix Resistor braking ...
Страница 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...
Страница 436: ...3AUA0000066143 Rev D EN EFFECTIVE 2018 01 01 Contact us www abb com drives www abb com drivespartners ...