Fault tracing 375
Embedded fieldbus faults
Embedded fieldbus faults can be traced by monitoring group
parameters. See also fault/alarm
No master device
If there is no master device on line, parameter
values remain unchanged.
What to do:
• Check that the network master is connected and properly configured.
• Check the cable connection.
Same device address
If two or more devices have the same address, parameter
value increases with every read/write command.
What to do:
• Check the device addresses. No two devices on line may have the same address.
Incorrect wiring
If the communication wires are swapped (terminal A on one device is connected to
terminal B on another device), parameter
value remains
unchanged and parameter
increases.
What to do:
• Check the RS-232/485 interface connection.
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...