200 Actual signals and parameters
2606
SWITCHING FREQ
1, 4, 8, 12, 16 kHz
-
4 kHz
Defines the switching frequency of the drive. Higher switching frequency results in
lower acoustic noise in the motor. See also parameter
and section
, I2N and ILD (= all currents) on page
In multimotor systems, do not change the switching frequency from the default value.
2607
SWITCH FREQ
CTRL
1, 2
-
1
Activates the switching frequency control. When active, the selection of parameter
is limited when the drive internal temperature increases.
See the figure below. This function allows the highest possible switching frequency at
a specific operation point.
Higher switching frequency results in lower acoustic noise in the motor, but higher
internal losses.
1 = ON – Active.
2 = ON (LOAD) – Switching frequency can adapt to loading instead of limiting the
output current. This allows maximum loading with all switching frequency
selections. The drive automatically decreases the actual switching frequency if
loading is too high for the selected switching frequency.
2608
SLIP COMP RATIO
0 … 200%
1
0
Defines the slip gain for the motor slip compensation control. 100% means full slip
compensation, 0% means no slip compensation. Other values can be used if a static
speed error is detected despite the full slip compensation.
Example:
35 Hz constant speed reference is given to the drive. Despite the full slip
compensation (SLIP COMP RATIO = 100%), a manual tachometer measurement
from the motor axis gives a speed value of 34 Hz. The static speed error is 35 Hz - 34
Hz = 1 Hz. To compensate the error, the slip gain should be increased.
0 = No slip compensation.
1…200 = Slip gain.
Group 26: Motor control
Code
Description
Range
Resolution
Default
S
* Temperature depends on the drive output frequency.
16 kHz
4 kHz
Drive
temperature
f
sw
limit
80…100 °C *
100…120 °C *
T
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...