Actual signals and parameters 247
4039 INT SETPNT
SEL
Selects the source for the selection of the internal setpoint
used as the process PID controller reference when
value is set to
.
Example:
=
Digital input DI2 = 1
->
is used as the reference.
NOT SEL
is used as the reference.
0
DI1
0 =
is used. 1 =
is used.
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
DI1,2
Selects with digital inputs DI1 and DI2 which internal
setpoint is used as the reference. 1 = DI active, 0 = DI
inactive.
7
DI2,3
See selection
.
8
DI3,4
See selection
.
9
DI4,5
See selection
.
10
is used. 1 =
is used.
15
TIMED FUNC 2 See selection
.
16
TIMED FUNC 3 See selection
.
17
TIMED FUNC 4 See selection
.
18
TIMED
FUN1&2
Selects with timed functions 1 and 2 which internal setpoint
is used as the reference. 1 = timed function active,
0 = timed function inactive.
19
41 PROCESS PID
SET 2
Process PID (PID1) control parameter set 2. See section
on page
4101 GAIN
See parameter
4102 INTEGRATION
TIME
See parameter
All parameters
No.
Name/Value
Description
Def/FbEq
DI1 DI2 Internal setpoint selected
0
0
1
0
0
1
1
1
Timed
function 1
Timed
function 2
Internal setpoint selected
0
0
1
0
0
1
1
1