246 Actual signals and parameters
DI4(INV)
See selection
-4
DI5(INV)
See selection
-5
4035 PID OUT
FREEZE
Freezes the output of the process PID controller. This
feature is useful when the reference is based on a process
actual value connected to an analog input, and the sensor
must be serviced without stopping the process.
The output of the PID controller is frozen as long as the
selected digital input is ON for parameter values
or OFF for parameter values
See also parameter
.
NOT SEL
Not selected
0
DI1
Output is frozen on the rising edge of digital input DI1.
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
DI1(INV)
Output is frozen on the falling edge of digital input DI1.
-1
DI2(INV)
See selection
-2
DI3(INV)
See selection
-3
DI4(INV)
See selection
-4
DI5(INV)
See selection
-5
4036 INTERNAL
SETPNT2
Selects a constant value as the process PID controller
reference, which becomes active when parameter
value is set to
and setpoint 2 is
selected with the input defined by parameter
.
40.0
x…x
Unit and range depend on the unit and scale defined by
parameters
and
.
-
4037 INTERNAL
SETPNT3
Selects a constant value as the process PID controller
reference, which becomes active when parameter
value is set to
and setpoint 3 is
selected with the input defined by parameter
.
40.0
x…x
Unit and range depend on the unit and scale defined by
parameters
and
.
-
4038 INTERNAL
SETPNT4
Selects a constant value as the process PID controller
reference, which becomes active when parameter
and setpoint 4 is
selected with the input defined by parameter
.
40.0
x…x
Unit and range depend on the unit and scale defined by
parameters
and
.
-
All parameters
No.
Name/Value
Description
Def/FbEq