Actual signals and parameters 213
3002 PANEL COMM
ERR
Selects how the drive reacts to a control panel
communication break.
Note:
When either of the two external control locations are
active, and start, stop and/or direction are through the
control panel –
= 8 (
) – the drive follows the speed
reference according to the configuration of the external
control locations, instead of the value of the last speed or
FAULT
Drive trips on fault
and the motor coasts to
stop.
1
CONST SP 7
The drive generates alarm
and sets the
speed to the speed defined by parameter
.
WARNING!
Make sure that it is safe to continue
operation in case of a panel communication break.
2
LAST SPEED
The drive generates alarm
and freezes the
speed to the level the drive was operating at. The speed is
determined considering the average speed and time.
WARNING!
Make sure that it is safe to continue
operation in case of a panel communication break.
3
3003 EXTERNAL
FAULT 1
Selects an interface for an external fault 1 signal.
NOT SEL
Not selected
0
DI1
External fault indication through digital input DI1. 1: Fault
trip (
). Motor coasts to stop. 0: No external
fault.
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
DI1(INV)
External fault indication through inverted digital input DI1. 0:
Fault trip (
). Motor coasts to stop. 1: No
external fault.
-1
DI2(INV)
See selection
-2
DI3(INV)
See selection
-3
DI4(INV)
See selection
-4
DI5(INV)
See selection
-5
3004 EXTERNAL
FAULT 2
Selects an interface for an external fault 2 signal.
See parameter
3005 MOT THERM
PROT
Selects how the drive reacts when the motor
overtemperature is detected.
NOT SEL
Protection is inactive.
0
All parameters
No.
Name/Value
Description
Def/FbEq