Parameters 283
Displays the actual parameter configuration checksum B.
The checksum B is generated and updated whenever an
action is selected in
and
, bit 9 = 1 (Approved checksum B)
The set of parameters for checksum B does not include:
• fieldbus settings
• motor data settings, and
• energy data settings parameters.
The parameters included in the checksum B calculation
are user editable parameters in parameter groups 10, 15,
19, 20, 21, 22, 23, 24, 25, 28, 30, 31, 32, 35, 36, 37, 40,
41, 46, 71, 95, 96, and 97.
See also section
Parameter checksum calculation
(page
0x0000
0x0000...0xffff
Actual checksum B.
1 = 1
Approved (reference) checksum A.
0x0000
0x0000...0xffff
Approved checksum A.
-
Approved (reference) checksum B.
0x0000
0x0000...0xffff
Approved checksum B.
-
Enables/disables a Modbus user to access a select set of
parameters using 550 register numbering.
See the supported parameters in section
supported by Modbus backwards compatibility with 550
on page
.
Disable
Using 550 compatibility mode is disabled
0
Enable
Using 550 compatibility mode is enabled
1
(Visible when user lock is open)
To change the current user pass code, enter a new code
into this parameter as well as
. A warning
will be active until the new pass
code is confirmed. To cancel changing the pass code,
close the user lock without confirming. To close the lock,
enter an invalid pass code in parameter
,
activate parameter
, or cycle the
power.
See also section
10000000
10000000…
99999999
New user pass code.
-
(Visible when user lock is open)
Confirms the new user pass code entered in
10000000…
99999999
Confirmation of new user pass code.
-
No.
Name/Value
Description
Default
FbEq 16
ACS180 FW.book Page 283 Tuesday, March 9, 2021 2:25 PM