Program features
92
Settings
Diagnostics
Actual position reset
You can reset the actual position value (
POS ACT PPU) by using the Homing
sequence or manually through parameters.
Homing sequence
The Homing function is used to calibrate the actual position value
PPU to a reference value. You have to do the homing sequence from the EXT1
control location. You have to configure parameter
HOMING SEL PTR to the
homing activation input, homing acknowledgement signal in parameters
HOMING ACK SEL and
HOMING ACK PTR. When the homing signal is active
and the drive is in EXT1, the message “HOMING ACTIVE” is displayed.
The homing reference has to be configured in parameter
HOMING REF. The
sign of the homing reference is only considered when the Start command does not
define the direction.
The Start command can be issued with the EXT1 start/stop control; you have to
decide the direction according to the present position and the homing
acknowledgement signal position
. The homing sequence will be completed
when the homing acknowledge signal gets activated and the drive stops
automatically. The message “HOMING DONE” will be displayed when the homing is
completed.
The actual position will be initialized to the position set in parameter
HOME
POSITION. For initializing the position value via the fieldbus, see application control
word
bit 1 on page
.
Manual reset of actual position
Manual reset of actual position
POS ACT PPU (mm) without running the
homing sequence:
Actual position value 02.21 is defined with par
HOME POSITION (0 mm by
default).
Parameter
Additional information
Settings of the position scale
Actual signals
Additional information
Actual Position
- EXT1 mode selected (stand-alone)
- Enable par
HOMING SEL PTR
+.000.000.00 -> C.1
- Enable par
HOMING ACK SEL
NOT SEL -> RESET
- Disable par
HOMING SEL PTR
C.1 -> +.000.000.00
- Disable par
HOMING ACK SEL
RESET -> NOT SEL
Содержание ACS 800 Series
Страница 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Страница 4: ......
Страница 26: ...Start up and control through the I O interface 26 ...
Страница 36: ...Quick start up guide 36 ...
Страница 52: ...Control panel 52 ...
Страница 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Страница 126: ...Program features 126 The figures below show speed limits according to different load conditions ...
Страница 128: ...Program features 128 ...
Страница 150: ...Application macros control location EXT1 EXT2 150 ...
Страница 228: ...Actual signals and parameters 228 ...
Страница 299: ...Adaptive Programming examples for crane control 299 ...
Страница 305: ...Adaptive Programming examples for crane control 305 ...
Страница 312: ...Adaptive Programming examples for crane control 312 The following figures show the previous example enlarged ...
Страница 314: ...Adaptive Programming examples for crane control 314 The following figures show the previous example enlarged ...
Страница 318: ...Analogue Extension Module 318 ...
Страница 332: ...Additional data actual signals and parameters 332 ...
Страница 333: ...DriveWindow 333 DriveWindow DriveWindow connected to the ACS800 RMIO RDCO board and channel CH3 ...
Страница 334: ...DriveWindow 334 ...
Страница 335: ...Control block diagrams 335 Control block diagrams ...
Страница 336: ...Control block diagrams 336 ...
Страница 337: ...Control block diagrams 337 ...
Страница 338: ...Control block diagrams 338 ...
Страница 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...