Actual signals and parameters
166
11.14
HOMING REF
Defines the speed reference in homing sequence. Value in rpm
.
The speed
reference sign is not considered if the Start command used defines the
direction also (For example, Par.
EXT1 STRT/STP/DIR configured as
DI1F, DI2R). The speed reference sign will be considered when Start
command does not define the direction (For example, Par.
EXT1 STRT/
STP/DIR configured as Par.
).
-18000 … 18000 rpm
Setting range
-180000 …
180000
12 STEP REFERENCING
Step referencing selection and values. An active step reference overrides the
drive speed reference.
12.01
STEP REF SEL
Activates the step reference or selects the activation signal.
NOT SEL
No step reference in use
1
DI3,4,5
Speed defined by digital input DI3, DI4 and DI5.
Any other combination of DI will activate STEP REF 1.
2
DI4,5,6
Speed defined by digital input DI4, DI5 and DI6. See DI3, 4, 5 selection.
3
DI7,8,9
Speed defined by digital input DI7, DI8 and DI9. See DI3, 4, 5 selection.
4
DI8,9,10
Speed defined by digital input DI8, DI9 and DI10. See DI3, 4, 5 selection.
5
DI9,10,11
Speed defined by digital input DI9, DI10 and DI11. See DI3, 4, 5 selection.
6
STEP POINTER
Speed defined by pointer selections Par.
, Par.
and Par.
. See
DI3, 4, 5 selection.
7
12.02
STEP REF 1
Defines speed 1. An absolute value. Does not include the direction information.
0 … 18000 rpm
Setting range
0 … 18000
12.03
STEP REF 2
Defines speed 2. An absolute value. Does not include the direction information.
-18000 … 18000 rpm
Setting range
-18000 …
18000
12.04
STEP REF 3
Defines speed 3. An absolute value. Does not include the direction information.
Note:
If inching is in use, the parameter defines the inching 1 speed. The sign
is taken into account. See chapter
-18000 … 18000 rpm
Setting range
-18000 …
18000
12.05
STEP REF 4
Defines speed 4. An absolute value. Does not include the direction information.
Note:
If inching is in use, the parameter defines the inching 2 speed. The sign
is taken into account. See chapter
-18000 … 18000 rpm
Setting range
-18000 …
18000
12.06
STEP DI1 PTR
Defines the source or constant for value Par.
of parameter
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
Parameter index or a constant value. See parameter
EXT1 STRT PTR
for information on the difference.
-
Index
Name/Selection
Description
FbEq
DI3
DI4
DI5
Operation
0
0
0
STEP REF 1
1
0
0
STEP REF 2
1
1
0
STEP REF 3
1
1
1
STEP REF 4
Содержание ACS 800 Series
Страница 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Страница 4: ......
Страница 26: ...Start up and control through the I O interface 26 ...
Страница 36: ...Quick start up guide 36 ...
Страница 52: ...Control panel 52 ...
Страница 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Страница 126: ...Program features 126 The figures below show speed limits according to different load conditions ...
Страница 128: ...Program features 128 ...
Страница 150: ...Application macros control location EXT1 EXT2 150 ...
Страница 228: ...Actual signals and parameters 228 ...
Страница 299: ...Adaptive Programming examples for crane control 299 ...
Страница 305: ...Adaptive Programming examples for crane control 305 ...
Страница 312: ...Adaptive Programming examples for crane control 312 The following figures show the previous example enlarged ...
Страница 314: ...Adaptive Programming examples for crane control 314 The following figures show the previous example enlarged ...
Страница 318: ...Analogue Extension Module 318 ...
Страница 332: ...Additional data actual signals and parameters 332 ...
Страница 333: ...DriveWindow 333 DriveWindow DriveWindow connected to the ACS800 RMIO RDCO board and channel CH3 ...
Страница 334: ...DriveWindow 334 ...
Страница 335: ...Control block diagrams 335 Control block diagrams ...
Страница 336: ...Control block diagrams 336 ...
Страница 337: ...Control block diagrams 337 ...
Страница 338: ...Control block diagrams 338 ...
Страница 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...