Actual signals and parameters
159
10.10
FAST STOP PTR
Defines the source or constant for the Fast Stop command. The command can
be a normally open (if the bit selection is not inverted) or normally closed (if the
bit selection is inverted) logic according to the selection in the pointer value.
When the command is active, the drive decelerates according to the parameter
Note:
For safety, it is better to use the bit selection as normally closed by
inverting the bit in the pointer value.
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
Parameter index or a constant value. See parameter
EXT1 STRT PTR
for information on the difference.
-
10.12
HIGHEND PTR
Defines the source or constant for the High-end limit command. The command
can be a normally open (if the bit selection is not inverted) or normally closed (if
the bit selection is inverted) logic according to the selection in the pointer
value. When the command is active, emergency stop in forward direction, stop
within time defined with Par.
EM STOP RAMP TIME.
Note:
For safety, it is better to use the bit selection as normally closed by
inverting the bit in the pointer value.
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
Parameter index or a constant value. See parameter
for information on
the difference.
-
10.13
LOWEND PTR
Defines the source or constant for the Low-end limit command. The command
can be a normally open (if the bit selection is not inverted) or normally closed (if
the bit selection is inverted) logic according to the selection in the pointer
value. When the command is active, emergency stop in reverse direction, stop
within time defined with Par.
Note:
For safety, it is better to use the bit selection as normally closed by
inverting the bit in the pointer value.
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
Parameter index or a constant value. See parameter
for information on
the difference.
-
10.14
SYNC SEL
Defines the Input for the Synchro command. When the command is active, and
the drive is in Master/Follower mode, the Shaft synchronisation is enabled. The
synchronisation should be enabled through the parameter
SYNCRO
CONTROL Synchro selection for this parameter to be used.
NOT SEL
No Synchro selection.
1
ENABLE
Synchro command always active.
2
COMM.MODULE
Synchro command through APPL CONTROL WORD (3.34) bit 0.
3
PARAM 10.17
SYNC PTR.
4
10.15
HOMING ACK SEL
Defines the Input for homing acknowledgment signal used in the homing
sequence. The signal initialises Actual Position PPU Par.
POS ACT
PPU. The value is initialised to value defined in Par.
when the drive is in homing sequence. The drive stops automatically on
receiving this command in homing sequence. For more details, see section
on page
Note:
Homing is activated only when the drive is controlled from EXT1.
NOT SEL
No selection.
1
RESET
Homing acknowledgment using the control panel. Automatically reverts back to
NOT SEL, once the acknowledgment is done.
2
COMM.MODULE
Homing Ackn command through (03.34) APPL CONTROL WORD bit 1.
3
PARAM 10.22
HOMING ACK PTR.
4
Index
Name/Selection
Description
FbEq
Содержание ACS 800 Series
Страница 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Страница 4: ......
Страница 26: ...Start up and control through the I O interface 26 ...
Страница 36: ...Quick start up guide 36 ...
Страница 52: ...Control panel 52 ...
Страница 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Страница 126: ...Program features 126 The figures below show speed limits according to different load conditions ...
Страница 128: ...Program features 128 ...
Страница 150: ...Application macros control location EXT1 EXT2 150 ...
Страница 228: ...Actual signals and parameters 228 ...
Страница 299: ...Adaptive Programming examples for crane control 299 ...
Страница 305: ...Adaptive Programming examples for crane control 305 ...
Страница 312: ...Adaptive Programming examples for crane control 312 The following figures show the previous example enlarged ...
Страница 314: ...Adaptive Programming examples for crane control 314 The following figures show the previous example enlarged ...
Страница 318: ...Analogue Extension Module 318 ...
Страница 332: ...Additional data actual signals and parameters 332 ...
Страница 333: ...DriveWindow 333 DriveWindow DriveWindow connected to the ACS800 RMIO RDCO board and channel CH3 ...
Страница 334: ...DriveWindow 334 ...
Страница 335: ...Control block diagrams 335 Control block diagrams ...
Страница 336: ...Control block diagrams 336 ...
Страница 337: ...Control block diagrams 337 ...
Страница 338: ...Control block diagrams 338 ...
Страница 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...