09 CDP CONTROL PANEL
3BHS212794 E01 REV M
ACS6000
USER MANUAL
210/278
9.2.3.1
Overview
If the parameter lock is disabled or unlocked (see “9.2.3.3 Enabling /
unlocking a parameter lock” on page 213) the parameters mode allows
entering the parameter settings for the required drive configuration
depending on the application.
The parameters are organized in functional groups, so called
parameter groups.
Note:
For details about the parameters, their settings and functions, see
“Appendix G – Signal and parameter table”.
When entering the parameters mode for the first time after the auxiliary
supply voltage of the drive has been switched on, the CDP control panel
displays the first parameter of parameter group 11. The next time the
parameters mode is entered, the previously selected parameter displays.
Some parameter settings cannot be changed while the drive is running. If
tried, the following warning displays.
Group
Description
Paramet
er
Description
Group 07 Control words
21.01
Start function
Group 08 Status words
21.02
Start function
Group 09 Fault and alarm words
21.03
Off1 stop mode
Group 11
Start, stop, direction or
MCB control
21.04
Process stop selection
Group 12 Reference selection
21.05
Process stop signal
Group 16 System control inputs
21.06
Process stop MCB control
Group 17
DC link control
21.07
Process stop mode
Group 18 Utility
.
Group 19 Data storage
.
Group 20 Limits
.
Group 21 Start / stop / process stop
21.17
MCB closing time limit
Group 22 Ramp functions
.
Group 23 Speed reference
21.19
MCB available signal
** WARNING **
WRITE ACCESS DENIED
PARAMETER SETTING
NOT POSSIBLE