![ABB ACS 6000 Скачать руководство пользователя страница 160](http://html.mh-extra.com/html/abb/acs-6000/acs-6000_user-manual_2952160.webp)
06 ELECTRICAL INSTALLATION
3BHS212794 E01 REV M
ACS6000
USER MANUAL
160/278
6.8.7.3
Routing optical fiber cables in an EXU cabinet with an ED5V, EB5R, EB5S, EB7P
or EB7Q type DCS800 converter
1.
Remove the acrylic protection cover in the cabinet.
2.
Unplug the DCS800 control panel.
Figure 6-37 DCS800 converter (ED5V, EB5R, EB5S, EB7P and EB7Q types)
3.
Insert a flat-blade screwdriver into one of the indentations at the
bottom of the removable cover.
4.
Gently press down the latch tab with the tip of the screwdriver and
pull the corner of the cover forward and repeat for the other side.
5.
Slide the removable cover up and then remove the cover.
6.
Connect the 2 optical fibers to the receptacles of channel CH0 (B) on
the COM-8x circuit board (A) according to the terminal numbers
printed on the marker sleeves.
Figure 6-38 COM-8x circuit board (A) in a DCS800 converter (ED5V, EB5R and
EB5S types) and a detail of channel CH0 (B) on the board.
(1) Control panel
(2) Indentation
(3) Removable cover
(4) Location of COM8x circuit board
1
2
2
3
4
CH0
A
B