272 Parameters
Differences in the default values between 50 Hz and 60 Hz
supply frequency settings
Parameter
bit 0
changes the
drive parameter default values according to the supply frequency, 50 Hz or
60 Hz. The bit is set according to the market before the drive is delivered.
If you need to change from 50 Hz to 60 Hz, or vice versa, change the value of the
bit and then do a complete reset to the drive. After that you have to reselect the
macro to be used.
The table below shows the parameters whose default values depend on the
supply frequency setting. The supply frequency setting, with the type
designation of the drive, also affects Group
parameter values
though these parameters are not listed in the table.
No
Name
bit
= 50 Hz
bit
= 60 Hz
1500.000
1800.000
1500.000
1800.000
1500.0
1800.0
-1500.00 rpm
-1800.00 rpm
1500.00 rpm
1800.00 rpm
-50.00 Hz
-60.00 Hz
50.00 Hz
60.00 Hz