manualshive.com logo in svg
background image

   4

9.  Connect the power cables

IEC connection diagram with shielded cables

NEC connection diagram with symmetrically shielded cable or conduit

Note:

 NEC installation can include separate insulated conductors inside a conduit, shielded VFD cable in conduit, or 

shielded VFD cable without conduit. The normal dashed symbol (c) in this diagram represents the shield of shielded VFD 

cable. The same solid symbol (b) represents conduit.

2. Use a separate grounding cable or a cable 

with a separate PE conductor for the line 

side, if the conductivity of the fourth 

conductor or shield does not meet the 

requirements for the PE conductor.

3. Use a separate grounding cable for the 

motor side, if the conductivity of the 

shield is not sufficient, or if there is no 

symmetrically constructed PE conductor 

in the cable.

4. 360-degree grounding of the cable shield 

is required for the motor cable. It is also 

recommended for the input power cable.

5. If necessary, install an external filter (du/

dt, common mode, or sine filter). Filters 

are available from ABB.

1.

Two protective earth (ground) conductors. Drive safety standard 

IEC/EN 61800-5-1 requires two PE conductors, if the cross-sectional 

area of the PE conductor is less than 10 mm

2

 Cu or 16 mm

2

 Al. For 

example, you can use the cable shield in addition to the fourth 

conductor.

PE

PE

L1

L2

L3

UDC+

U1

W1

M

3

T1/U T2/V T3/W

V1

(PE)

(PE)

L1

L2

L3

PE

UDC-

1

2

3

4

4

5

3. Shield of a VFD shielded cable: Ground the 

shield 360° under drive's grounding clamp, 

then twist with the ground conductors and 

connect under the drive's ground terminal. 

Ground the shield also 360° at the motor 

end, then twist and connect under the 

motor's ground terminal. For a conduit 

installation see b.

4. Symmetrically constructed grounding 

conductors inside a VFD shielded cable: 

Twist together, combine with the shield 

and connect under the drive's ground 

terminal and under the motor's ground 

terminal. For a conduit installation see a.

 

5. If necessary, install an external filter (du/dt, 

common mode, or sine filter). Filters are 

available from ABB.

Note:

 All openings in the drive enclosure must 

be closed with UL listed devices having the 

same Type rating as the drive Type.

1.

Insulated ground conductor in a conduit: Ground to drive's PE 

terminal and to the distribution panel ground bus. For a VFD cable 

installation see d.

2. Conduit ground: Bond the conduit to the drive's conduit box and to 

the distribution panel enclosure. For a VFD cable installation see c

.

PE

PE

L1

L2

L3

U1

W1

M

3

T1/U T2/V T3/W

V1

L1

L2

L3

PE

3

UDC-

UDC+

5

4

4

1

2

3

Содержание ACQ580-31 Series

Страница 1: ...ive when a rotating permanent magnet motor is connected to it A rotating permanent magnet motor energizes the drive including its input and output terminals Make sure that debris from drilling cutting...

Страница 2: ...pair cable for analog signals Use double shielded or single shielded cable for the digital relay and I O signals Do not run 24 V and 115 230 V signals in the same cable Protect the drive and input pow...

Страница 3: ...creases the insulation resistance If you think that there is moisture dry the motor and do the measurement again Frame Symmetrically grounded TN S systems center grounded wye Corner grounded delta and...

Страница 4: ...l area of the PE conductor is less than 10 mm2 Cu or 16 mm2 Al For example you can use the cable shield in addition to the fourth conductor PE PE L1 L2 L3 UDC U1 W1 M 3 T1 U T2 V T3 W V1 PE PE L1 L2 L...

Страница 5: ...strated in the applicable figure 3c Slide the cables through the holes in the cable entry and attach the grommets to the holes 4 Connect the power cables For the tightening torques refer to Terminal d...

Страница 6: ...ound the motor cable shield at the motor end For minimum radio frequency interference ground the motor cable shield 360 degrees at the cable entry of the motor terminal box 4b 4c 2 9 N m 2 9 N m 2 N m...

Страница 7: ...SCR1 terminal 3 Tie all control cables to the provided cable tie mounts Default I O connections Water default Total load capacity of the auxiliary voltage output 24V X2 10 is 6 0 W 250 mA 24 V DC Term...

Страница 8: ...cluded in the delivery 12 Install the cover s 1 7 N m R3 R8 R6 1 7 N m 15 lbf in 2 N m 1 5 lbf ft 2 N m 2 N m 2 N m 1 5 lbf ft 1 2 1 2 IP21 UL Type 1 R3 IP55 UL type 12 R3 IP21 UL type 1 R6 R8 IP55 UL...

Страница 9: ...cable shield and connect them to the grounding terminals Ground the shield 360 degrees at the grounding clamp If you use discrete conductors connect the insulated ground conductor to the ground termin...

Страница 10: ...Home screen press Menu to enter the Main Menu 5 In the Main menu go to Parameters Complete list 95 HW configuration pressing Select repeatedly to select parameter 95 01 6 In parameter 95 01 Supply vol...

Страница 11: ...Communication control Refresh settings Validates any changed EFB configuration settings Use this after changing any parameters in group 58 58 14 Communication loss action 58 17 Transmit delay 58 28 EF...

Страница 12: ...hree current carrying conductors in raceway or cable or earth directly buried For other conditions size the cables according to local safety regulations appropriate input voltage and the load current...

Страница 13: ...14 321 023A 4 R3 17 0 23 0 23 0 15 JJS 35 10 473 027A 4 R6 24 27 27 20 JJS 40 8 625 034A 4 R6 29 34 34 25 JJS 50 8 711 044A 4 R6 34 44 44 30 JJS 60 6 807 052A 4 R6 44 52 52 40 JJS 80 4 960 065A 4 R6...

Страница 14: ...ides all other functions of the drive Wiring The safety contacts must open close within 200 ms of each other Double shielded twisted pair cable is recommended for the connection The maximum length of...

Страница 15: ...fety function is used for safety component functionality Adjustable speed electrical power drive systems Part 5 2 Safety requirements Functional Safety of machinery Functional safety of safety related...

Отзывы: