4 EN – Quick installation guide
EN
DA
DE
ES
FI
FR
FR
NL
PL
PT
RU
SV
TR
ZH
Check if capacitors need to be reformed
Reform the capacitors if the drive has not been powered up (either in storage or
unused) for a year or more.
You can determine the manufacturing date from the serial number, which you find on
the type designation label attached to the drive. The serial number is of format
XYYWWRXXXX. YY and WW tell the manufacturing year and week as follows:
YY:
17, 18, 19, … for 2017, 2018, 2019,
…
WW:
01, 02, 03, … for week 1, week 2, week 3,
…
For information on reforming the capacitors, see
Converter modules with
electrolytic DC capacitors in the DC link capacitor reforming instructions
(3BFE64059629 [English]), available on the Internet at
.
Data
IEC ratings
Select the power cables
See
on page
Ensure cooling
See
on page
. No condensation or frost is allowed. The allowed operating
temperature range of the drive without derating is -15 to +40 °C.
ACH580-31-
Cable Cu (mm
2
)
aR fuse
Losses
(W)
3-phase
U
N
= 400 V
09A5-4
3×2.5+2.5
170M1561
226
12A7-4
3×2.5+2.5
170M1561
329
018A-4
3×2.5+2.5
170M1563
395
026A-4
3×6+6
170M1563
579
033A-4
3×10+10
170M1565
625
039A-4
3×10+10
170M1565
751
046A-4
3×16+16
170M1566
912
062A-4
3×25+16
170M1567
1088
073A-4
3×35+16
170M1568
1502
088A-4
3×50+25
170M1568
1904
106A-4
3×70+35
170M1569
1877
145A-4
3×95+50
170M1570
2963
169A-4
3×120+70
170M5809
3168
206A-4
3×150+70
170M5810
3990
3AXD00000586715