![ABB ACH550-UH HVAC Скачать руководство пользователя страница 292](http://html.mh-extra.com/html/abb/ach550-uh-hvac/ach550-uh-hvac_user-manual_3045265292.webp)
1-292
ACH550-UH User’s Manual
Maintenance
Note:
If there is a risk of the dust entering adjoining equipment, perform the cleaning
in another room.
4. Replace the cooling fan.
5. Restore power.
Drive module fan replacement
The drive module fan cools the heatsink. Fan failure can be predicted by the
increasing noise from fan bearings and the gradual rise in the heatsink temperature
in spite of heatsink cleaning. If the drive is operated in a critical part of a process, fan
replacement is recommended once these symptoms start appearing. Replacement
fans are available from ABB. Do not use other than ABB specified spare parts.
To monitor the running time of the cooling fan, see
on page
Frame Sizes R1
…
R4
To replace the fan:
1. Remove power from drive.
2. Remove drive cover.
3. For Frame Size:
•
R1, R2: Press together the retaining clips on the fan
cover sides, and lift.
•
R3, R4: Press in on the lever located on the left side
of the fan mount, and rotate the fan up and out.
4. Disconnect the fan cable.
5. Install the fan in reverse order.
6. Restore power.
X0021
3
4
2
Содержание ACH550-UH HVAC
Страница 2: ......
Страница 8: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 32: ...1 32 ACH550 UH User s Manual Installation ...
Страница 66: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 186: ...1 186 ACH550 UH User s Manual Parameters ...
Страница 190: ...1 190 ACH550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...
Страница 333: ...ACH550 UH User s Manual 1 333 Technical data ...