![ABB ACH550-UH HVAC Скачать руководство пользователя страница 220](http://html.mh-extra.com/html/abb/ach550-uh-hvac/ach550-uh-hvac_user-manual_3045265220.webp)
1-220
ACH550-UH User’s Manual
Embedded fieldbus
•
To convert from ABB PI gains to Siemens
P and I gains:
•
To convert from Siemens P and I gains to ABB PI gains:
Point database
The following table lists the point database for FLN / ACH550 (Application 2734).
FLN Point Database
Point
Subpoint Name
Factory
Default
Engr.
Units
Slope
Intercept
On Text
Off Text
#
Type
(SI Units)
01
LAO
CTLR ADDRESS
99
-
1
0
-
-
02
LAO
APPLICATION
2734
-
1
-
-
{03}
LAI
FREQ OUTPUT
0
Hz
0.1
0
-
-
{04}
LAI
PCT OUTPUT
0
PCT
0.1
0
-
-
{05}
LAI
SPEED
0
RPM
1
0
-
-
{06}
LAI
CURRENT
0
A
0.1
-
-
{07}
LAI
TORQUE
0
PCT
0.1
-200
-
-
{08}
LAI
POWER
0
(0)
HP
(KW)
0.134
0.1
0
0
-
-
{09}
LAI
DRIVE TEMP
77
(25)
°
F
(
°
C)
0.18
(0.1)
32
0
-
-
{10}
LAI
DRIVE KWH
0
KWH
1
-
-
{11}
LAI
DRIVE MWH
0
MWH
1
-
-
{12}
LAI
RUN TIME
0
HRS
1
-
-
{13}
LAI
DC BUS VOLT
0
V
1
-
-
{14}
LAI
OUTPUT VOLT
0
V
1
-
-
{15}
LAI
PRC PID FBCK
0
PCT
0.1
-
-
{16}
LAI
PRC PID DEV
0
PCT
0.1
-
-
{17}
LAI
MOTOR TEMP
77(25)
°
F (
°
C)
1.8 (1)
32 0
-
-
{18}
LAI
MREV
COUNTER
0
MREV
1
0
-
-
20
LAO
OVRD TIME
1
hrs
1
0
-
-
{21}
LDI
FWD.REV ACT
FWD
-
1
0
REV
FWD
{22}
LDO
FWD.REV CMD
FWD
-
1
0
REV
FWD
P GAIN
Siemens
= PI GAIN
ABB
x 0.0015
I GAIN
Siemens
=
PI GAIN
ABB
PI GAIN
ABB
x 0.0015
P GAIN
ABB
= PI GAIN
Siemens
x 667
I GAIN
ABB
=
PI GAIN
Siemens
PI GAIN
Siemens
x 667
Содержание ACH550-UH HVAC
Страница 2: ......
Страница 8: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 32: ...1 32 ACH550 UH User s Manual Installation ...
Страница 66: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 186: ...1 186 ACH550 UH User s Manual Parameters ...
Страница 190: ...1 190 ACH550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...