Chapter 4 – Programming
4-4
ACS/ACH 400 Direct N2 Bus Interface
1 OEM Application ID and
Revision
This parameter shows the application software
ID and revision code. First two digits are the ID
and next two are the revision code. The
Application ID for N2 software is 10.
2 Drive ID-number
This parameter selects the node number for the
ACS/ACH 400 drive on the N2 Bus. Default
value is 0, which disables the communication.
3 Communication time-out
time
This parameter is used to define the time-out
value for the communication loss function. If the
Metasys system does not communicate with
the drive for this period of time, a
communication loss fault is generated.
4 Communication Fault
Function
This parameter selects what is being done
when there is a communication loss from the
Metasys system down to the drive. The
communication loss is defined so that if there
are no messages to the drive within a time
period defined in the parameter 8
TIME-OUT SELECT, a communication loss is
generated.
The possible selections are:
0 = NOT SELECTED
Ignore
The communication loss is ignored.
1 = FAULT
Stop the Drive
The drive will show the
OEM
fault on the panel
and will stop. The drive will also go to the Off-
Line state on the N2 Bus. To restart the drive,
communication must be restored and the fault
must be cleared.
7 Framing Error
Counter
5307 OEM
APP PAR7
0 –
65535
Number of detected
framing errors
8 Overrun
Counter
5308 OEM
APP PAR8
0 –
65535
Number of detected
overrun errors
9 Protocol Soft-
ware Error
5309 OEM
APP PAR9
0 – 3
Protocol software
error code
Parameter
Panel Text
Range/
Unit
Description