![ABB ACH 400 Скачать руководство пользователя страница 25](http://html.mh-extra.com/html/abb/ach-400/ach-400_user-manual_2921025.webp)
Chapter 4 – Programming
ACS/ACH 400 Direct N2 Bus Interface
4-3
Binary Output
The binary output points support the following
features:
•
Binary Output value
•
Override value is used to change the
Binary Output value. It is not possible to
return to the previous value by removing
the override. The override feature is
used only to change the value.
Communication
Setup
To activate the direct N2 Bus connection, set
parameter 5005 PROTOCOL SEL to OEM
APPLIC (4). If you can not see this selection on
the panel, your drive does not have N2 protocol
software in the application memory.
For the direct N2 Bus communication there are
new setup parameters on the drive. These are
located in the group 53 OEM APPLICATION.
These parameters are shown in Table 4-1
“Group 53 OEM APPLICATION”.
Table 4-1 Group 53 OEM APPLICATION
Parameter
Panel Text
Range/
Unit
Description
1 OEM Applica-
tion ID and
Revision
5301 OEM
APP PAR1
1010 -
1099
N2 Software ID and
revision
2 Drive ID-num-
ber
5302 OEM
APP PAR2
1 - 255
Drive N2 address
3 Communication
time-out time
5303 OEM
APP PAR3
1 – 600
(1.0 -
60.0 s)
Time limit for
communication loss
detection
4 Communication
fault function
5304 OEM
APP PAR4
0 – 3
Operation in case
communication with
master device is lost
5 Good Message
Counter
5305 OEM
APP PAR5
0 –
65535
Rolling counter for
good messages
6 Bad Message
Counter
5306 OEM
APP PAR6
0 –
65535
Communication error
counter
Содержание ACH 400
Страница 1: ...User s Guide N2 Protocol ACS ACH 400 AC Drives ABB Drives ...
Страница 2: ......
Страница 4: ......
Страница 8: ...Safety Instructions vi ACS ACH 400 Direct N2 Bus Interface ...
Страница 36: ...Chapter 5 Fault Tracing 5 4 ACS ACH 400 Direct N2 Bus Interface ...
Страница 43: ......