The electric current is computed by using the formula:
I = 4.65V / ((Cable DCR * Length of Network) +
(Contact DCR * Number of Contacts)).
Where Cable DCR = 0.0216 ohms/ft, Contact DCR = 0.001 ohms, and Number of
Contacts = 128 (because each taps has two contacts in series). The Cable DCR is
determined using an ambient of 80
°
C, and temperature coefficient of
0.00393 per
°
C.
Flat Cable
shows the physical configuration of Flat cable.
Figure 10. Flat Cable Physical Configuration