![ABB AC 800M Скачать руководство пользователя страница 68](http://html1.mh-extra.com/html/abb/ac-800m/ac-800m_user-manual_3372088068.webp)
Bus connector
Section 3 Fieldbus Topologies
68
3BDS009029R5001 B
transmit signals. The Sub-D plug, connected to the Sub-D connector of the device,
needs only the receive and transmit signals for the communication transmission.
The connector shown below include a terminating resistor that can be turned on and
off.
This type of connector can be used equally well at the beginning, end or middle of a
PROFIBUS segment. The terminating resistor must be turned on in the connector
for the first / last device on the bus segment. It must be turned off for the devices in
the middle.
Figure 23. PROFIBUS connector
One connector with a PG socket should be used in the most accessible spot (at the
beginning or end) for each line on every segment. This connector makes it
possible to attach a diagnostic device for service access.
Be sure that the connector type used is suitable for the selected transmission rate.
Содержание AC 800M
Страница 1: ...Power and productivity for a better worldTM AC 800M PROFIBUS DP Installation System Version 5 0 5 1...
Страница 2: ......
Страница 3: ...AC 800M PROFIBUS DP Installation System Version 5 0 5 1...
Страница 8: ...Table of Contents 8 3BDS009029R5001 B...
Страница 16: ...Released User Manuals and Release Notes About This User Manual 16 3BDS009029R5001 B...
Страница 29: ...Section 2 Transmission Technology RS485 network limits 3BDS009029R5001 B 29 Figure 2 RS485 network limits...
Страница 56: ...Calculation of transmission delay time TTD Section 2 Transmission Technology 56 3BDS009029R5001 B...
Страница 116: ...Updates in Revision Index B 116 3BDS009029R5001 B...
Страница 117: ......